Basic Functions
177
B
as
ic
Func
tio
ns
7.13.3
User V/F Pattern Operation
The iS7 inverter allows the configuration of user-defined V/F patterns to suit the load
characteristics of a specific motor.
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
BAS
07
V/F pattern
V/F Pattern
2 User V/F
0
–
2
-
41
User frequency 1 User Freq 1
15.00
0
–
Maximum
frequency
Hz
42
User voltage 1
User Volt 1
25
0
–
100%
%
43
User frequency 2 User Freq 2
30.00
0
–
Maximum
frequency
Hz
44
User voltage 2
User Volt 2
50
0
–
100%
%
45
User frequency 3 User Freq 3
45.00
0
–
Maximum
frequency
Hz
46
User voltage 3
User Volt 3
75
0
–
100%
%
47
User frequency 4 User Freq 4
60
0
–
Maximum
frequency
Hz
48
User voltage 4
User Volt 4
100
0
–
100%
%
User V/F pattern Setting Details
Code
Description
BAS-41 User Freq 1
–
BAS-48 User Volt 4
Sets the parameter values to assign user-defined frequencies (User Freq x)
for the start and maximum frequencies. Voltages can also be set to
correspond with each frequency, and for each user voltage (User Volt x).