Peripheral Devices
92
5.1.3
Dynamic Braking Unit (DBU) and Resistor
Dynamic Braking Unit Specifications
UL form Type
Voltage
Capacity of
applied motor
Braking unit
Reference-
Terminal
arrangement &
dimensions
UL type
Type A
(For resistance of
DB resistors,
refer to
on page
.)
200 V
30
–
37 kW
SV370DBU-2U
Group 1
45
–
55 kW
SV550DBU-2U
75 kW
SV370DBU-2U, 2Set
400 V
30
–
37 kW
SV370DBU-4U
45
–
55 kW
SV550DBU-4U
75 kW
SV750DBU-4U
90 kW
SV550DBU-4U, 2Set
110
–
132 kW
SV750DBU-4U, 2Set
160 kW
SV750DBU-4U, 3Set
Non UL
type
Type B
(For resistance of
DB resistors,
refer to the DB
Unit manual)
200 V
30
–
37 kW
SV037DBH-2
Group 2
400 V
30
–
37 kW
SV037DBH-4
45
–
55 kW,
75 kW
SV075DBH-4
SV075DB-4
Group 3
185
–
220 kW
SV2200DB-4 Note 1)
Group 4
280
–
375 Kw
SV2200DB-4, 2Set
Type C
(For resistance of
DB resistors,
refer to the DB
Unit manual)
200 V
30
–
37 kW
LSLV0370DBU-2LN
Group 5
LSLV0370DBU-2HN
Group 6
45
–
55 kW,
75 kW
LSLV0750DBU-2LN
Group 5
LSLV0750DBU-2HN
Group 6
400 V
30
–
37 kW
LSLV0370DBU-4LN
Group 5
LSLV0370DBU-4HN
Group 6
45
–
55 kW,
75 kW
LSLV0750DBU-4LN
Group 5
90 kW
LSLV0900DBU-4HN
Group 6
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...