Technical Specifications
13
2.6
Product Specification Details
2.6.1
Control
Items
Description
Control
Control modes
V/F control, V/F PG, slip compensation, sensorless vector-1,
sensorless vector-2, vector control
Frequency
settings resolution
Digital command: 0.01 Hz
Analog command: 0.06 Hz (maximum frequency: 60 Hz)
Frequency
accuracy
Digital command: 0.01% of maximum output frequency
Analog command: 0.1% of maximum output frequency
V/F pattern
Linear, square reduction, user V/F
Overload capacity
Rated current for heavy duty operation: 150% for 1 min
Rated current for normal duty operation: 110% for 1 min
Torque boost
Manual torque boost, automatic torque boost
•
Only the heavy load ratings apply to 0.75-22 kW model types without a built-in DC resistor
(NON-DCR)
.
2.6.2
Operation
Items
Description
Operation
Operation types
Select from keypad, terminal strip, or network communication
operation.
Frequency
settings
Analog type: -10
–
10 V, 0
–
10 V, 0
–
20 mA
Digital type: keypad
Operation
function
•
PID control
•
3-wire operation
•
Frequency limit
•
Second function
•
Reverse rotation prevention
•
Inverter bypass
•
Flying start
•
Power braking
•
Up-down operation
•
DC braking
•
Frequency jump
•
Slip compensation
•
Automatic restart
•
Automatic tuning
•
Energy buffering
•
Flux braking
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...