M
oni
to
r
Func
tio
ns
317
Using Monitor Functions
Code
Description
10
Over
Voltage
Outputs a signal when the inverter DC link voltage rises
above the protective operation voltage.
11
Low Voltage Outputs a signal when the inverter DC link voltage drops
below the low voltage protective level.
12
Over Heat
Outputs signal when the inverter overheats.
13
Lost
Command
Outputs a signal when there is a loss of analog input
terminal and RS-485 communication command at the
terminal block.
Outputs a signal when communication power is present
and an I/O expansion module is installed. It also outputs a
signal when losing analog input and communication
power commands.
14
RUN
Outputs a signal when an operation command is entered
and the inverter outputs voltage.
No signal output during DC braking.
15
Stop
Outputs a signal at operation command off, and when
there is no inverter output voltage.
16
Steady
Outputs a signal in steady operation.
17
Inverter Line
Outputs a signal while the motor is driven by the inverter
line.
18
Comm Line
Outputs a signal when multi-function input terminal
(switching) is entered.
Group Code
LCD Display Initial Setting
Unit
IN
65-72 Px Define
16 Exchange
-
OUT
32
Relay 2
15 Inverter Line -
33
Q1 Define
16 Comm Line -
For details, refer to
19
Speed
Search
Outputs a signal during inverter speed search operation.
For details, refer to
20
Step Pulse
Outputs a signal when a step is completed in an auto
sequence operation.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...