Basic Functions
188
overvoltage fault trip may occur.
•
Note that if a free run stop is used, the actual deceleration time may be longer than the preset
deceleration time.
7.18
Frequency Limit
The operation frequency can be limited by setting a maximum frequency, start frequency,
upper limit frequency, and lower limit frequency.
7.18.1
Frequency Limit Using Maximum Frequency and Start
Frequency
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
DRV
19
Start frequency
Start Freq
0.50
0.01
–
10.00
Hz
20
Maximum frequency Max Freq
60.00
40.00
–
400.00
Hz
Frequency Limit Using Maximum Frequency and Start Frequency - Setting Details
Code
Description
DRV-19 Start Freq
Sets the lower limit value for all speed unit parameters that are expressed in
Hz or rpm. Any operation frequency input that is lower than the start
frequency is treated as a 0 Hz input.
DRV-20 Max Freq
Sets an upper limit frequency to all speed unit parameters that are expressed
in Hz or rpm, except for the base frequency (DRV-18). An operation frequency
cannot be set higher than the maximum frequency.
7.18.2
Frequency Limit Using Upper and Lower Limit Frequency
Values
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
24
Frequency limit
Freq Limit
0
--- No ----
No/Yes
-
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...