Communication Function
382
11.13.4.2
Inverter Control Area Parameter (Reading and Writing Available)
Address Parameter
Scale unit Bit allotment
0h0380
note1)
Frequency
command
0.01
Hz
Command frequency setting
0h0381
RPM command 1
rpm command RPM setting
0h0382
Operating
command
-
-
B7 Reserved
B6 Reserved
B5 Reserved
B4 Reserved
B3 0
1: Free run stop
B2 0
1: Trip reset
B1 0:Reverse command 1:Forward command
B0 0:Stop command 1:Run command
Ex) Forward operating command: 0003h,
Reverse operating command: 0001h
0h0383
Accelerating time 0.1
sec
Accelerating time setting
0h0384
Decelerating
time
0.1
sec
Decelerating time setting
0h0385
Virtual digital
input control
(0:Off, 1:On)
-
-
BI5 Virtual DI 16 (COM85)
BI4 Virtual DI 15 (COM84)
BI3 Virtual DI 14 (COM83)
BI2 Virtual DI 13 (COM82)
BI1 Virtual DI 12 (COM81)
BI0 Virtual DI 11 (COM80)
B9 Virtual DI 10 (COM79)
B8 Virtual DI 9 (COM78)
B7 Virtual DI 8 (COM77)
B6 Virtual DI 7 (COM76)
B5 Virtual DI 6 (COM75)
B4 Virtual DI 5 (COM74)
B3 Virtual DI 4 (COM73)
B2 Virtual DI 3 (COM72)