Communication Function
369
<Response>
Field Name
Slave Address
Function*
Exception Code
CRC Lo
CRC Hi
* Function value is the set value of the highest bit of the query function value.
11.13.3
iS7/iS5/iG5/iG5A Compatible Common Area Parameter
Address Parameter
Scale nit
R/W Assigned content by bit
0h0000 Inverter model -
-
R
B: iS7
0h0001 Inverter capacity -
-
R
0: 0.75 kW 1: 1.5 kW
2: 2.2 kW
3: 3.7 kW 4: 5.5 kW
5: 7.5 kW
6: 11 kW 7: 15 kW
8: 18.5 kW
9: 22 kW 10: 30 kW
11: 37 kW
12: 45 kW 13: 55 kW
14: 75 kW
15: 90 kW 16: 110 kW
17: 132 kW
18: 160 kW 19: 200 kW
20: 220 kW
21: 280 kW 22: 375 kW
65535: 0.4 kW
0h0002
Inverter input
voltage
-
-
R
0: 220 V class
1: 400 V class
0h0003 Version
-
-
R
Ex.) 0x0100: Version 1.00
0x0101: Version 1.01
0h0004 Reserved
-
-
R/W -
0h0005
Command
frequency
0.01 Hz
R/W -
0h0006
Operating
command
(option)
* Refer to
additional
description
-
-
R
B15 Reserved
B14 0: Keypad Freq
1: Keypad Torq
2-16: Terminal block Multi-step speed
17: Up 18: Down 19: STEADY
20: AUTO-A 21: AUTO-B 22: V1
23: I1 24: V2
25: I2
26: Reserved 27: Built-in485
28: Communication option
B13
B12
B11
B10
B9
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...