Peripheral Devices
90
AC Reactor Specifications
You can install an AC reactor to prevent the capacitors and generators from overheating or
being damaged when the power source voltage is unbalanced.
When you install an AC reactor, connect the AC reactor cables to the R, S, and T terminals on
the inverter. Installation of an AC reactor is not necessary if a DC reactor is already installed in
the inverter.
To avoid power loss resulting from the incorrect installation of an AC reactor, contact LS
ELECTRIC Customer Support to ensure that your model type and application requires the
installation of an AC reactor.
Refer to the following specifications tables to choose an appropriate AC reactor for your
application.
Inverter capacity
AC reactor specifications
Heavy duty
Normal duty
mH
A
mH
A
0008iS7-2
2.13
5.7
1.20
10
0015iS7-2
1.20
10
0.88
14
0022iS7-2
0.88
14
0.56
20
0037iS7-2
0.56
20
0.39
30
0055iS7-2
0.39
30
0.28
40
0075iS7-2
0.28
40
0.20
59
0110iS7-2
0.20
59
0.15
75
0150iS7-2
0.15
75
0.12
96
0185iS7-2
0.12
96
0.10
112
0220iS7-2
0.10
112
0.07
160
0300iS7-2
0.07
160
0.05
200
0370iS7-2
0.05
200
0.044
240
0450iS7-2
0.044
240
0.038
280
0550iS7-2
0.038
280
0.026
360
0750iS7-2
0.026
360
0.02
500
0008iS7-4
8.63
2.8
4.81
4.8
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...