7.1.3.1
Setting a Frequency Reference for 0
–
10 V Input
Set IN-
06 (V1 Polarity) to “0
(unipolar)”. Use a voltage output from an external source or use the
voltage output from the VR terminal to provide inputs to V1. Refer to the diagrams below for
the wiring required for each application.
[External source application]
[Internal source (VR) application]
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
DRV
07
Frequency reference
source
Freq Ref Src 2
V1
0
–
9
-
IN
01
Frequency at
maximum analog
input
Freq at 100%
Maximum
frequency
0.00
–
max. frequency Hz
05
V1 input monitor
V1
Monitor[V]
0.00
0.00
–
10.00
V
06
V1 polarity options
V1 Polarity
0
Unipolar
0
–
1
-
07
V1 input filter time
constant
V1 Filter
10
0
–
10000
ms
08
V1 minimum input
voltage
V1 volt x1
0.00
0.00
–
10.00
V
09
V1 output at
minimum voltage (%)
V1 Perc y1
0.00
0.00
–
100.00
%
10
V1 maximum input
voltage
V1 Volt x2
10.00
0 .00
–
10.00
V
11
V1 output at
maximum voltage
(%)
V1 Perc y2
100.00
0
–
100
%
16
Rotation direction
options
V1 Inverting 0
No
0
–
1
-
17
V1 quantizing level
V1
Quantizing
0.04
0.00*, 0.04
–
10.00
%
*
Quantizing is disabled if “0” is selected.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...