Communication Function
384
Address Parameter
Scale unit Bit allotment
Limit
0h0395
Torque Bias
0.1
%
Torque Bias
0h0395
–
0h399
Reserved
-
-
-
0h039A Anytime Para
-
-
CNF-20 value setting
0h039B Monitor Line-1
-
-
CNF-21 value setting
0h039C Monitor Line-2
-
-
CNF-22 value setting
0h039D Monitor Line-3
-
-
CNF-23 value setting
- Note1) A frequency set via communication using the iS7 common area frequency address (0h0380,
0h0005) is not saved even when used with the parameter save function. To save a changed
frequency to use after a power cycle, follow these steps:
- Set DRV-07 to Keypad-1 and select a random target frequency.
- Cmd Frequency (DRV-01, 0h1101): Set the frequency via communication into the parameter area
frequency address (0h1101).
- Parameter Save
(0h03E0): Set to “1” before
turning off the power.
- The frequency set via communication will be displayed after turning the power off and on again.