M
oni
to
r
Func
tio
ns
299
Using Monitor Functions
9
Using Monitor Functions
9.1
Monitoring the Operating Status via the Keypad
You can monitor the operating status using the keypad of the inverter. You can select the
desired items to monitor in Config mode (CNF), view three items at a time in Monitor mode,
and select an item on the status display.
9.1.1
Selecting Monitor Mode Display
Mode
Group
Code
LCD Display
Parameter Setting
Unit
CNF
-
21
Monitor Line-1 0
Frequency
Hz
-
22
Monitor Line-2 2
Output Current
A
-
23
Monitor Line-3 3
Output Voltage
V
24
Mon Mode Init 0
No
-
Monitor Mode Display Selection Details
Code
Description
CNF-21
–
23
Monitor Line-x
Select the items to monitor in Monitor mode. Monitor mode is displayed when
the inverter is powered on. Also, all three items in Monitor Line-1
–
3 can be
displayed simultaneously.
Select an item for the line to display. If “Yes” is set at
CNF-24 (Mon Mode Init), CNF-21
–
23 will be initialized.
Setting
Function
0
Frequency
Displays the set frequency while stopped. During
operation, it displays the actual output frequency
(Hz).
1
Speed
Displays the set speed (rpm) while stopped. During
operation, it displays the actual operating speed
(rpm).
2
Output Current Displays the output current.
3
Output Voltage Displays the output voltage.
4
Output Power
Displays the output power.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...