Basic Functions
185
B
as
ic
Func
tio
ns
7.17.2
Stop after DC Braking
When the operation frequency reaches the set value during deceleration (DC braking
frequency) the inverter stops the motor by supplying DC power to the motor. With a stop
command input, the inverter begins decelerating the motor. When the frequency reaches the
DC braking frequency set at ADV-17, the inverter supplies DC voltage to the motor and stops it.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
ADV
08
Stop mode
Stop Mode
0
Dec
0
–
4
-
14
Output block time
before braking
DC-Block Time 0.10
0.00
–
60.00
sec
15
DC braking time
DC-Brake Time 1.00
0
–
60
sec
16
DC braking amount
DC-Brake Level 50
0
–
200
%
17
DC braking frequency DC-Brake Freq 5.00
0.00
–
60.00
Hz
Note
DC braking does not produce stop torque. Install appropriate peripheral devices if stop torque is
required in your application.
DC Braking After Stop Setting Details
Code
Description
ADV-14 DC-Block
Time
Sets the time to block the inverter output before DC braking. If the inertia of the
load is great, or if the DC braking frequency (ADV-17) is set too high, a fault trip
may occur due to overcurrent conditions when the inverter supplies DC voltage
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...