Starting up the device - CANopen interface
Leuze electronic GmbH + Co. KG
CML 730i
101
Blanking settings (group 7)
Parameter
Index
(hex.)
Sub-
index
(hex.)
Data
type
Access
Min.
value
Max. value Default Explanation
Number of teach cycles
2103
1
t08U
RO
10
Depending on the environ
-
mental conditions or applica
-
tion, the light curtain may
have completed multiple
cycles after the triggering of a
teach.
Type of storage for teach values
2103
2
t08U
RW
0
1
0
0: Non-volatile storage of
teach values
1: Teach values only saved
while voltage ON
Sensitivity adjustment for teach event
2103
3
t08U
RW
0
3
0
Sensitivity of the measure
-
ment system:
0: High function reserve (for
stable operation)
1: Medium function reserve
2: Low function reserve
3: Transparent media
Switching threshold
2103
4
t08U
RW
10
98
75
Threshold as percentage of
teach threshold (50% = func
-
tion reserve 2)
Teach status
2400
1
t08S
RO
0
MAX_T08U
Information about the last
teach:
00: Teach ok
01: Teach busy
80: Teach error (bit 8 = error
bit)
Up to 4 beam areas can be deactivated. Deactivated beams can be assigned the logical
values 0, 1 or the value of the adjacent beam. With auto blanking activated, up to 4 beam areas
are automatically suppressed during teaching.
Auto blanking should only be activated during commissioning of the CML 700i to suppress inter
-
fering objects. In process mode, auto blanking should be deactivated.
For details on this topic see chapter 15.4.
NOTICE
Perform teach after changing the blanking configuration!
Perform a teach after changing the blanking configuration.
A teach can be performed via the receiver control panel or via the teach command.