Jetter AG
575
JC-120MC
Automatic copying of controller data
Parameter value 5
Number of the last register or flag
Allowed values
All valid numbers from the memory area of the
corresponding JC-120MC which are equal to or greater
than the value for
First
Illegal values
Invalid numbers
Numbers less than
First
In the event of an illegal
value
The controller stores only one value (First).
Example
[COMMAND_11]
Command = DaFileWrite
DaFile = /SD/MyTestData2.da
Append = 0
Type = Register
First = 1000000
Last = 1000000
[COMMAND_12]
Command = DaFileWrite
DaFile = /SD/MyTestData2.da
Append = 1
Type = Flag
First = 10
Last = 20
[COMMAND_13]
Command = DaFileWrite
DaFile = /SD/MyTestData2.da
Append = 1
Type = Register
First = 1000001
Last = 1000999
The following commands are available for access via network using FTP:
Command = FtpConnect
Function
Establishing a connection to an FTP server
Parameter name 1
ServerAddr
Parameter value 1
IP address or name of FTP server
Allowed values
IP address of the FTP server
Name which can be resolved through DNS
Illegal values
IP address other than that of the FTP server
Name which cannot be resolved
Parameter name 2
UserName
Parameter value 2
User name for logging on at the FTP server
Parameter name 3
Password
Parameter value 3
Password for logging on at the FTP server
In the case of a illegal
values
The controller does not establish the connection. It
enters the error into the log file.
Available commands for
access via FTP
Summary of Contents for JC-120MC
Page 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Page 18: ......
Page 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Page 160: ......
Page 186: ......
Page 196: ......
Page 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Page 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Page 586: ......
Page 604: ......
Page 633: ......