260
Jetter AG
10 Programming
Controller evaluates errors reported by a remote network node
The controller has got read access to the contents of the following status
registers of all network nodes at the Jetter Ethernet system bus.
The contents are accessed via registers 39nnn0 through 39nnn5.
(GNN: nnn = 001 ... 199).
Registers
JX3-BN-ETH,
JX3-COM-EIPA
Controller
Error register
200008
39nnn0
Enhanced error register 1
200009
39nnn1
Enhanced error register 2
200010
39nnn2
JetSync status
240010
39nnn3
Subscriber status
250000
39nnn4
Subscription ID
250002
39nnn5
The operating system writes the ID of the subscription for which last an error
has been reported to register 250002.
If the value of register 39nnn0 is unequal zero, an error has occurred. A
network node has reported this error to the controller via its status registers.
In consequence, the operating system of the controller reacts by taking the
following steps:
Step
Description
1
The operating system sets bit 10 in R 200009.
2
If ...
... or ...
... then ...
... Bit x = 1 of
R 200009,
Bit x = 1 of
R 200010,
... the operating system sets bit
7 of R 200008.
3
The operating system enters the GNN of the network node having last
reported an error to the controller into R 394001.
4
The operating system enters the IP address of the network node having
last reported an error to the controller into R 394002.
5
The operating system enters the port number of the network node having
last reported an error to the controller into R 394003.
By means of NetCopy commands, you can precisely locate the error and fix
the root cause. This works, because GNN, IP address and port number of the
other network node are known.
Make sure the contents of registers 39nnn0 through 39nnn5 are read by the
application program. Further registers having got a value unequal zero
indicate that further network nodes have reported an error. Make sure you
also clear these errors.
Access to the status
registers
Locating faults
Fixing the root cause
Summary of Contents for JC-120MC
Page 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Page 18: ......
Page 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Page 160: ......
Page 186: ......
Page 196: ......
Page 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Page 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Page 586: ......
Page 604: ......
Page 633: ......