Jetter AG
361
JC-120MC
Programming
Assigning LEDs
By default, LEDs located in HMI keys are assigned to a register which is
overlaid by special flags.
You can set the number of the register from which the LED state is read out
via registers in multi-display mode.
HMI
Register
Default LED register
number
Flag numbers
Single display
-
203143
2224 ... 2235
1
MR 2833
203143
2224 ... 2235
2
MR 2834
203143
2224 ... 2235
3
MR 2835
203143
2224 ... 2235
4
MR 2836
203143
2224 ... 2235
Here, the assignments between keys, special flag and overlaid register are
listed. This assignment list applies to single-display mode and default settings
of multi-display mode.
LED in the key
Flag
Register bit
[F1]
2224
203143.0
[F2]
2225
203143.1
[F3]
2226
203143.2
[F4]
2227
203143.3
[F5]
2228
203143.4
[F6]
2229
203143.5
[F7]
2230
203143.6
[F8]
2231
203143.7
[F9]
2232
203143.8
[F10]
2233
203143.9
[F11]
2234
203143.10
[F12]
2235
203143.11
Introduction
Register/flag numbers
Assignment
Summary of Contents for JC-120MC
Page 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Page 18: ......
Page 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Page 160: ......
Page 186: ......
Page 196: ......
Page 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Page 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Page 586: ......
Page 604: ......
Page 633: ......