Jetter AG
531
JC-120MC
Programming
The function
CanOpenAddEmergencyTx()
lets you set the bits in this
register.
The structure of the
Error Register object
is shown in the following table.
Index
Subindex
Default
Description
0x1001 0
0
Error register (read-only)
This object implements the CANopen® error register functionality.
The following error messages may appear:
Bit 0 = Generic error
Bit 1 = Current error
Bit 2 = Voltage error
Bit 3 = Temperature error
Bit 4 = Communication error (overrun, error state)
Bit 5 = Specific device profile error
Bit 6 = Reserved (always 0)
Bit 7 = Manufacturer-specific error
The structure of the
Pre-defined Error Field object
is shown in the following
table.
Index
Subindex
Default
Description
0x1003 0
0
Number of errors entered in the array's
standard error field
1
0
Most recent error
0 indicates no error
2 ... 254
-
Earlier errors
This object shows a history list of errors that have been detected by the
device. The maximum length of the list is 254 errors. The list content is
deleted on restart.
Composition of standard error field
2-byte LSB: Error code
2-byte MSB: Additional information
The structure of the
Manufacturer Device Name object
is shown in the
following table.
Index
Subindex
Default
Description
0x1008 0
device name
Hardware name
Error Register object
(index 0x1001)
Pre-defined Error Field
object (index 0x1003)
Manufacturer Device
Name object (index
0x1008)
Summary of Contents for JC-120MC
Page 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Page 18: ......
Page 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Page 160: ......
Page 186: ......
Page 196: ......
Page 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Page 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Page 586: ......
Page 604: ......
Page 633: ......