294
Jetter AG
10 Programming
Setting the startup delay
If other devices connected to the bus have got a longer startup time, the boot
process must be delayed.
To set the delay time, proceed as follows:
Step
Action
1
Switch on the device JC-120MC.
2
Enter the password. For this, write value 1112502132 (0x424f6f74) to
R 202970.
3
Enter the desired delay time in steps of 100 ms into register 202971.
Result:
The next boot process will be delayed by the set startup delay time
before initializing the JX2 and JX3 system bus.
Password register
Enter 1112502132 (0x424F6F74) into this register. Then enter the desired
value into the startup delay time register. Now, the controller sets the value of
this register to 0.
Register properties
Value
1112502132 (0x424F6F74)
Startup delay time
Write into this register the delay time in multiples of 100 milliseconds.
Register properties
Values
0 (OFF) ... 3,000 (300 seconds)
Value after reset
As described above (remanent)
The controller only executes start delay, when switch S11 is in
RUN
position.
Start delay is terminated by leaving the
RUN
position.
LED
D1
flashing slowly during the first half of the start delay time
(approx. 1 Hz).
LED
D1
flashing fast during the second half of the start delay time
(approx. 4 Hz).
Introduction
Set delay time
R 202970
R 202971
Procedure
Display
Summary of Contents for JC-120MC
Page 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Page 18: ......
Page 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Page 160: ......
Page 186: ......
Page 196: ......
Page 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Page 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Page 586: ......
Page 604: ......
Page 633: ......