![Jetter JC-120MC User Manual Download Page 58](http://html1.mh-extra.com/html/jetter/jc-120mc/jc-120mc_user-manual_3870525058.webp)
58
Jetter AG
4 Mechanical and electrical installation
The table below shows the possible states of the OS-LEDs
R
,
E
,
D1
und
D2
:
LED
State
Description
R
OFF
No power supply or failure
1Hz
Either the controller does not boot up, or it does not
execute the application program.
4Hz
Reset or fatal error
ON
Application program is being executed
E
OFF
No error
1Hz
No valid OS
4Hz
Reset, fatal error, or checking the network consistency
ON
Error; refer to error register
D1
OFF
Normal operating condition
1Hz
Automatic IP configuration, or AutoCopy function is
completed, or first part of startup delay is carried out.
4Hz
Reset or second part of startup delay is carried out, or
fatal error has occurred.
ON
File
autocopy.ini
on SD card is being executed.
D2
OFF
Boot loader is not running
1Hz
Boot loader: Automatic IP configuration
4Hz
Reset or fatal error
ON
Boot loader is being executed
States of the OS LEDs
Summary of Contents for JC-120MC
Page 1: ...User Manual JC 120MC Controller 60880901 We automate your success...
Page 18: ......
Page 40: ...40 Jetter AG 3 Identifying Hardware revisions see page 38 Related topics...
Page 160: ......
Page 186: ......
Page 196: ......
Page 485: ...Jetter AG 485 JC 120MC Programming Topic Page Programming 486 Registers 498 Contents...
Page 521: ...Jetter AG 521 JC 120MC Programming Use 29 bit identifier Default 11 bit identifier...
Page 586: ......
Page 604: ......
Page 633: ......