SmartAXIS Touch User's Manual
22-23
5 User Communication
22
Communication
●
User Communication Protocol Settings Dialog Box
The command for user communication protocol is collectively managed in the User Communication Protocol Settings
dialog box.
■
Protocol Name
Enter the name of the user communication protocol. The maximum number for protocol name is 40 characters.
■
Receiving Character Time Out (x100 msec)
Specify the time out value (0 to 255) from when 1 frame of data has been received to when the next frame of data
starts to be received. A frame refers to a data string from the beginning to the end of a command. If the Receiving
Character Time Out is set to 0, it is not monitored. These setting items are used only with receive command.
Example
:
When the received data (1 frame) is 2 bytes,
While
ON is selected as
Trigger Type
in
Trigger
Condition
and LM100 is set to
Device
, LM101 is set to
Completed Device
, and LDR110 is set to
Status
Device
The data of second byte starts to be received before exceeding the Receiving Character Time Out duration
after the data of first byte is received, and the values of the Completed Device and Status Device when
receiving of the data has been successfully completed are as follows.
• The value of the Completed Device LM101 changes to 1.
When the
Not Clear Completed Device automatically
check box is not selected, when the value of
the Trigger Condition device LM100 changes from 0 to 1, the value of the Completed Device LM101
changes to 0.
When the
Not Clear Completed Device automatically
check box is selected, the value of Completed
Device LM101 remains 1, so set 0 if necessary.
• The value of the Receiving Character Time Out (0, bit 15) of the Status Device LDR110 remains
0.
You cannot use the following characters in the protocol name.
\
/
: , ; * ? " < > |
Value of Receiving Character Time Out
(0, bit 15)
of Status Device LDR110
Value of Completed Device
LM101
Receive command
Value of LM100 when
Trigger Condition is While ON
1
0
1
0
1
0
Receiving Character Time Out duration
First byte of receive data
Second byte of receive data
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...