2 Word Devices
27-10
SmartAXIS Touch User's Manual
LSD20
When a value of 1 is written into this device address, the internal clock in Touch is updated
according to the data stored in LSD21 to 26. It automatically resets to 0 after the update.
LSD21
Stores preset value in the Touch internal clock "Year". (2 BCD digits)
LSD22
Stores preset value in the Touch internal clock "Month". (2 BCD digits)
LSD23
Stores preset value in the Touch internal clock "Day". (2 BCD digits)
LSD24
Stores preset value in the Touch internal clock "Hour". (2 BCD digits)
LSD25
Stores preset value in the Touch internal clock "Minute". (2 BCD digits)
LSD26
Stores preset value in the Touch internal clock "Second". (2 BCD digits)
LSD27
Current value of the scan time for Touch (msec)
LSD28
Minimum value of the scan time for Touch (msec)
LSD29, 30
Reserved
LSD31
Stores the currently displayed screen number.
LSD32
Set a value (in reference to a Base Screen number you want to switch to) and it will
automatically switch to a specified Base Screen number.
Note, after switching to a Base Screen, the value stored automatically resets to 0.
LSD33
USB flash drive error status
0: Normal
1: USB flash drive not inserted/incompatible memory
2: Formatting error
3: Access error/insufficient free space/read-write failure
LSD34
USB flash drive available capacity lower word (kB)
LSD35
USB flash drive available capacity upper word (kB)
LSD36
USB flash drive full capacity lower word (kB)
LSD37
USB flash drive full capacity upper word (kB)
LSD38
Ladder program or FBD program processing time (msec)
LSD39 to 48
Reserved
LSD49
O/I Link Slave station number
LSD50
The sequence value of the message number (or channel number if the alarm function is
being used) selected by the cursor in the Alarm List Display is stored.
A value of between 1 and 1024 (allocated using ((project No. - 1) x 16 + bit po 1)) is
stored for the number.
LSD51
Color or Monochrome LCD models: Brightness Adjustment 0 to 31
LSD52
The ID number of the script for which the error occurred
LSD53
Script error status
LSD54
Reserved
LSD55
Monochrome LCD models: Contrast Adjustment 0 to 31
LSD56
The number of lines of data from the start line to the line currently selected with the cursor
displayed in the Alarm List Display/Alarm Log Display is stored.
LSD57
The number of log data pieces stored in the Data Storage Area by the Alarm Log function is
stored. (0 to 1,024)
LSD58
USB flash drive download status
During download of a file to USB flash drive with WindO/I-NV3 the following bits turns ON.
When downloading is complete, the bit turns OFF.
Bit 2: Recipe data
Bit 4: Project data
LSD59 to 66
Reserved
LSD67
Stores the connection status for TCP clients and the TCP server for the User Communication
set to the Ethernet interface.
Bit 0: User Communication 1
Bit 1: User Communication 2
Bit 2: User Communication 3
Address
Function/Part
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...