4 Using the Data
14-34
SmartAXIS Touch User’s Manual
10
Select the specification method for the amount of data to copy in
Number of Data
.
■
Value
Use a constant.
Specifies the amount to copy (1 to 64).
■
Device
Use a word device.
Specifies the source word device. You can only specify an internal device.
Click
to display the Device Address Settings dialog box. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-62.
11
Select the order to copy data in
Stored Order of Data
.
■
From Newest to Oldest
Of the data to copy, copies from the start point in order of the newest data first.
■
From Oldest to Newest
Of the data to copy, copies from the start point in order of the oldest data first.
12
Select the data to copy from the data in
Target Data
.
Select the
Sampling Time
check box to copy the sampling time data from the data.
Select the
Value of Device
check box to copy the value of device from the data. When not copying the value of
device, proceed to step
15
.
13
Select the specification method for the data number to copy the value in
Data No.
.
■
Value
Use a constant.
■
Device
Use a word device.
14
Specify the data number of the data to start copying out of the data to copy with
Start No.
.
If you select
Value
, specify the data number (1 to 128).
If you select
Device
, specify the source device. You can only specify an internal device. Click
to display the
Device Address Settings dialog box. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-62.
When the
Sampling Time
check box is selected, the data number is 1. This cannot be changed.
15
Specify the data number of the data to end copying out of the data to copy with
End No.
.
If you select
Value
, specify the data number (1 to 128).
If you select
Device
, specify the source device. You can only specify an internal device. Click
to display the
Device Address Settings dialog box. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-62.
16
Select the condition to start copying in
Trigger Condition
.
■
Always
Copies each time the data is updated.
■
Device
Specifies the device that triggers the start of copying the data. Copies the data when the value of the specified device
changes from 0 to 1. Click
to display the Device Address Settings dialog box. For the device address configuration
procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-62.
17
Click
OK
to close the Individual Settings dialog box.
The maximum amount of data that can be copied to the internal device is 64.
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...