SmartAXIS Touch User’s Manual
13-19
3 Alarm Log Settings Dialog Box
13
Alarm Log Function
■
Channel Settings
The trigger condition for the channel is configured here.
Alarm function:
Selects whether or not to use the alarm function.
Enable:
Monitors the state of the device configured for the channel and samples
the alarm information.
Disable:
Does not monitor the state of the device. No Alarm Log data is created.
NO/NC:
Selects the alarm detection condition.
NO:
The alarm occurs when the monitored bit changes from 0 to 1.
NC:
The alarm occurs when the monitored bit changes from 1 to 0.
Lock/Unlock:
Selects whether or not to automatically recover based on the state of the monitored bit.
Lock:
Even if the monitored bit returns the normal state, the alarm remains
active until the key button
CHECK
is pressed.
Unlock:
The alarm is automatically recovered from based on the bit state when the
monitored bit returns the normal state.
Example: When
NO/NC
is
NO
Press
CHECK
Record confirmation time
Record recovery time
Record occurrence time
Unlock
Record confirmation time
Record recovery time
No operation
Record occurrence time
Lock
0
1
0
1
Monitored bit
Alarm occurred
The display on the Alarm List Display disappears when the alarm is recovered from, regardless of the
Lock/
Unlock
setting. To keep displaying the alarm until
CHECK
is pressed, use the Alarm Log Display.
Text ID:
To use text registered in Text Manager as the message to display when an alarm occurs,
select this check box and specify the Text Manager ID number to use as the message.
Number of blocks x 16 (number of channels) text IDs are used starting from the set ID
number.
Click
to open Text Manager where you can edit the text.
Text:
Shows the text for the specified text ID.
Reference Screen No.: Specifies the screen number (1 to 3000) to display when the key button
Ref.
is pressed.
Number of blocks x 16 (number of channels) screens are used starting from the screen
number.
This option can only be configured when
Base Screen
or
Popup Screen
is selected in
Reference Screen
.
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...