SmartAXIS Touch User’s Manual
13-17
3 Alarm Log Settings Dialog Box
13
Alarm Log Function
■
Settings
The Alarm Log settings for each channel are edited here.
■
Auto
Batch registers or changes the settings for all the channels.
Click this button to open the Auto-Setup dialog box. The Auto-Setup dialog box settings are reflected in all the
channels.
For details, refer to “Auto-Setup Dialog Box and Individual Settings Dialog Box” on page 13-18.
■
Edit
Registers or changes, the settings for the selected channel.
Select a channel, and then click this button to open the Individual Settings dialog box. The settings for the selected
channel are reflected in the Individual Settings dialog box.
For details, refer to “Auto-Setup Dialog Box and Individual Settings Dialog Box” on page 13-18.
No.:
Displayed as (Block No.)-(Channel No.). Double clicking the cell opens the Individual Settings
dialog box.
Source:
Shows the bit device or bit of the word device to monitor. Double clicking the cell opens the
Device Address Settings dialog box.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-62.
Data:
Shows whether or not to save Alarm Log data in the date storage area.
Double clicking the cell switches between
Store
and
No Store
.
Alarm function:
Shows whether or not the alarm function is used. Double clicking the cell switches between
Enable
and
Disable
. Channels switched to
Disable
cannot be configured. Device states are
not monitored and Alarm Log data is not created.
NO/NC:
Shows the alarm detection condition. Double clicking the cell switches between
NO
and
NC
.
Lock/Unlock:
Shows whether or not to automatically recover based on the state of the monitored bit.
Double clicking the cell switches between
Lock
and
Unlock
.
Text ID:
Shows the Text Manager ID number (1 to 32000) to use for the message displayed when an
alarm occurs. Double clicking the cell allows you to specify the Text Manager ID number.
Text Message:
Shows the text for the specified text ID. Double clicking the cell opens Text Manager.
Reference Screen No.: Shows the screen number to display when the key button
Ref.
is pressed. Double clicking the
cell opens the Individual Settings dialog box.
This option can only be configured when
Base Screen
or
Popup Screen
is selected in
Reference Screen
.
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...