![IDEC SmartAXIS Touch FT1A Series User Manual Download Page 1015](http://html.mh-extra.com/html/idec/smartaxis-touch-ft1a-series/smartaxis-touch-ft1a-series_user-manual_6173871015.webp)
SmartAXIS Touch User's Manual
22-53
5 User Communication
22
Communication
■
Variable
Select this check box to store data up to either
Constant (Character)
data, or
Constant (Hexadecimal)
data
from the beginning of the received data in a device. Stores data of the size specified under
Words
.
When the stored data is smaller than the size specified under
Words
, the values of all remaining devices will stored 0.
When the check box is not selected, the amount of data (bytes) stored is Number of bytes x Number of words.
Examples: Device for receive command data
Example 1
When the trigger condition is satisfied, the received data is stored in devices in the following order.
Example 2
When the trigger condition is satisfied, the received data is stored in devices in the following order.
3231h
LDR100:
3433h
LDR101:
0000h
LDR102:
1
(31h)
Value of Device
2
(32h)
3
(33h)
4
(34h)
Number of specified words: 3
Number of words for stored data: 2
The stored data is smaller than the size specified for Words.
No
conversion
Stored data
Insufficient by 1 word
0 is stored.
When the
Variable
check box is selected, observe the following points.
• When data is set expect for the end of a command, set
Constant (Character)
data or
Constant
(Hexadecimal)
data following
Device
data.
• When there is no data stored in the device, all of the values of devices specified under
Words
will be 0.
• The maximum amount of the received data stored in the device is Number of bytes x Number of words.
Item
Setting
Conversion Type
No Conversion
Device
LDR100
Use Reference Device
OFF
Storage Method of data
from Upper byte
Number of bytes
1
Words
3
Variable
OFF
Item
Setting
Conversion Type
No Conversion
Device
LDR100
Use Reference Device
OFF
Storage Method of data
from Lower byte
Number of bytes
2
Words
2
Variable
OFF
3100h
LDR100:
3200h
LDR101:
3300h
LDR102:
No conversion
1
(31h)
Upper
Lower
Value of Device
0
(00h)
2
(32h)
0
(00h)
3
(33h)
0
(00h)
Received data
1
(31h)
2
(32h)
3
(33h)
Order of reception
Words: 3
from Upper byte
1 byte
from Lower byte
2 bytes
3231h
LDR100:
3433h
LDR101:
No conversion
2
(32h)
Upper
Lower
Value of Device
1
(31h)
4
(34h)
3
(33h)
Received data
1
(31h)
2
(32h)
3
(33h)
4
(34h)
Order of reception
Words: 2
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...