This chapter describes internal devices available for the SmartAXIS.
The Touch includes an internal HMI device to control HMI functions, and control device for control functions.
1.1 HMI Device Addresses
■
HMI Internal Relay (LM)
This is a bit-unit device used for the HMI function. It can store 2,048 addresses.
■
HMI Keep Relay (LK)
This is a bit-unit device that holds the values of device used for the HMI function. The value of this device can be set
to 0 by clearing the project data download option or online function, or it becomes zero if the backup battery is
drained. The address range can be varied between 1,024 and 8,192. For details, refer to Chapter 16 “Minimum and
Maximum Amount of Data Storage and Number of Addresses” on page 16-2.
■
HMI Temporary Relay (LBM)
This is a bit-unit device for temporarily storing values for the HMI function. The value of this device switches between
screens and text groups and user accounts, and it becomes 0 if the screen is reset. It can store 128 addresses.
■
HMI Special Internal Relay (LSM)
Special functions are assigned to each bit by the bit-unit device. It can store 64 addresses.
Chapter 27
Internal Devices
1
Bit Devices
Internal Device Name
Symbol
R/W
Address Range
Base
HMI Internal Relay
LM
R/W
0 to 2,047
10
HMI Keep Relay
LK
R/W
Variable
10
HMI Temporary Relay
LBM
R/W
0 to 127
10
HMI Special Internal Relay
LSM
R/W
0 to 63
10
HMI Timer Relay
LTC
R
0 to 31
10
R/W stands for Read/Write. R/W enables reading and writing of values, whereas R enables reading only.
Address
Function/Part
LSM0
Normally set to 1.
LSM1
1 only on the second scan when Base Screen is switched.
It also operates when switching text group or user account, or resetting the display screen.
LSM2
1 only on the first scan when Base Screen is switched.
It also operates when switching text group or user account, or resetting the display screen.
LSM3
0 only on the first scan when Base Screen is switched.
It also operates when switching text group or user account, or resetting the display screen.
LSM4
Alternates between 0 and 1 on each scan of the Touch.
LSM5
1 only on the first scan when Popup Screen is opened.
LSM6
1 while touch panel is pressed.
LSM7
Alternates between 0 and 1 each time data is read (read scan) from all the external devices being
used.
LSM8
After powering ON value is 1 until the initially displayed screen switches to another screen.
LSM9
When value changes from 0 to 1, the backup data stored in flash memory is restored.
When it becomes 1 value does not become 0 until the Touch is reset or 0 is written.
LSM10
When value changes from 0 to 1, the data of Keep Relay and Keep Register configured in the Data
Storage Area, and the current backlight settings are transferred to flash memory.
When it becomes 1 value does not become 0 until the Touch is reset or 0 is written.
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...