SmartAXIS Touch User's Manual
3-81
4 Special Functions
3
Pr
oject
4.12 Analog Input
This section describes how to configure analog input signals such as those from pressure sensors.
●
Feature Description
The Touch is equipped with two analog inputs.
The FT1A-*12RA-* accepts analog input of 0 to 10V DC by converting it to 0 to 1000 digital values.
The FT1A-*14KA-* and the FT1A-*14SA-* accepts analog input of 0 to 10V DC or 4 to 20 mA by converting it to 0 to
1000 digital values. The converted analog input values are stored in special data registers. Inputs that are not
specified as analog inputs are digital inputs. For the on or off judgment threshold value when digital input is specified,
refer to Chapter 29 “SmartAXIS Specifications” on page 29-1.
●
Applicable Models
The type analog input that can be used varies based on the model.
●
Storage Locations for the Analog Input Value and Analog Input Status
The Touch has two embedded analog inputs. The digitally converted analog input values are stored in special data
registers (D8040 and D8041: read-only) as values between 0 and 1,000. The analog input status is also stored in
special data registers (D8042, D8043, and D8077: read-only). These values are updated with each scan.
■
Analog Input Status (D8077)
If the analog input signal exceeds 11 V or 21 mA, the corresponding bit of D8077 turns on to indicate overflow. For
details, refer to Chapter 27 “2.2 Control Device Addresses” on page 27-12.
■
Analog Input Status (D8042, D8043)
Details on the analog input status (D8042, D8043) are as follows.
Analog input
FT1A-*14KA-*
FT1A-*14SA-*
FT1A-*12RA-*
0 to 10 V
YES
YES
4 to 20 mA
YES
NO
Analog input terminal
AI0
AI1
Special data register that stores the analog input value
D8040
D8041
Special data registers that store the analog input status
D8077
D8042
D8077
D8043
Status
Description
Analog input value
0
Operating normally
Current analog input value
1
Converting data (occurs only once during the initial
conversion when the power is turned on)
Undefined value
2
Initializing
0
3
Parameter setting error
Correct value immediately before the error
occurred
4
Reserved
―
5
Wiring fault (out of maximum range)
Analog input signals exceed 11 V, or 21 mA
Maximum
6
Wiring fault (out of minimum range, open current loop)
Analog input signals fall below 2 mA
Minimum
7 to 65535
Reserved
―
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...