SmartAXIS Touch User’s Manual
13-21
3 Alarm Log Settings Dialog Box
13
Alarm Log Function
■
Batch
Select this check box to batch output all the sampled data to the external memory.
All the data is saved on the external memory when the trigger devices changes from 0 to 1. If a file with the same
name already exists on the external memory, that file is overwritten. The maximum amount of output data is the
amount configured by the data storage area.
*1 Advanced mode only
Touch
Alarm Log data (CSV)
Output to
USB flash drive
USB flash drive
Alarm Log data
0
1
Trigger Device
Ch.No.
Message
Occurrence Time
Recovery Time
Confirmation Time
1-1
Voltage drop
12/01/2011 12:00:05
12/01 12:01:10
12/01 12:01:30
1-2 Temperature abnormal
12/01/2011 12:01:09
12/01 12:02:21
12/01 12:02:55
1-1
Voltage drop
12/01/2011 12:02:00
12/01 12:03:11
12/01 12:05:12
1-3
Overcurrent
12/01/2011 12:30:21
12/01 12:55:15
12/01 13:00:00
1-1
Voltage drop
12/01/2011 12:45:36
12/01 12:53:12
12/01 12:57:41
Data to be output (all)
Output stops if there is insufficient free space on the external memory. USB flash drive error information is
stored in HMI Special Data Register LSD33.
Trigger Device:
Specifies the bit device or bit of the word device to serve as condition for batch output. For the
device address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on
page 2-62.
Data is output to file when the trigger device changes from 0 to 1.
File Name:
Enter the file name for the output data or shows the file name.
The default is “ALMHTO.CSV”. To change the file name, enter a new file name. The maximum
number is 120 characters (including the extension).
Add Device data to File Name
Select this check box to add the bottom three digits of
the value of device configured by
File Name Device
to
the end of the file name for the output data.
Example: When the value of device configured by
File
Name Device
is 123, the file name is
“ALMHTO123.CSV”.
File Name Device:
Specifies the word device that is the source for the value
to add to the file name. For the device address
configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-62. This option can only be
configured when the
Add Device data to File Name
check box is selected.
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...