SmartAXIS Specifications
■
FT1A-*14KA/14SA
*1 This value may vary by device.
Calibration or Verification to Maintain Rated Accuracy
Not possible
Maximum Permanent Allowed Overload (No Damage)
28.8V DC
Overload Status (Outside Input Range) Detection
Detectable
Isolation
Between input terminals
Not isolated
Between input and internal circuit
Not isolated
Used as Digital
Input
Digital Input Type
— (IEC 61131-2 digital input type is not supported)
Input Threshold
ON voltage: 15V min. (ON current: 0.20 mA min.)
OFF voltage: 5V max. (OFF current: 0.06 mA max.)
Input Signal Type
Voltage/current input (selectable with software)
Input Points
(Terminal No. /Common Line Name)
1 point in 1 common line
AI0+, AI1+/ AI0-, AI1-
Input Range
0 to 10V DC (Voltage Input)
4 to 20mA (Current Input)
Input Impedance
78.0K
Ω
(Voltage Input)
250
Ω
(Current Input)
Digital Resolution
0 to 1,000 (850 steps)
Data Type
Binary data: 0 to 1000
Input Value of LSB
11.7mV (Voltage Input)
16
μ
A (Current Input)
Type of Input
Single-ended input
AD Conversion
Sample Duration Time
2 msec max.
Sample Repetition Time
2 msec max.
Total Input System Transfer Time
3 msec + filtering time + scan time (Voltage Input)
12 msec + filtering time + scan time (Current Input)
Input Error
Maximum Error at 25°C
±3.0% of full scale
Temperature Coefficient
±0.04%/°C of full scale
Maximum Error
±5.0% of full scale
General
Characteristics
Operating Mode
Self-scan
Conversion Method
SAR
Status Display
Device Monitor screen (LCD)
Maximum Temporary Error during Electrical Noise Tests
±5.0% of full scale
Recommended Cable for Noise Immunity
Twisted pair shielded cable
Calibration or Verification to Maintain Rated Accuracy
Not possible
Maximum Permanent Allowed Overload (No Damage)
28.8V DC (Voltage Input)
40mA (Current Input)
Overload Status (Outside Input Range) Detection
Detectable
Isolation
Between input terminals
Not isolated
Between input and internal circuit
Not isolated
Used as Digital
Input
Digital Input Type
— (IEC 61131-2 digital input type is not supported)
Input Threshold
ON voltage: 15V min. (ON current: 0.20 mA min.)
OFF voltage: 5V max. (OFF current: 0.06 mA max.)
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...