2. Wiring
77
1) Stop supplying external motor power at emergency stop input
Note 1 The rating for the emergency stop signal to turn ON/OFF at contact CR1 is 24V DC
and 10mA or less.
Note 2 Connect such as a connector to L1/L2/L3 terminals when cutting off the motor power
source externally.
(This controller is not equipped with internal drive cutoff relay.)
Note 3 It is the contact output to control the drive cutoff device connected externally. The
rating is 30V DC and 200mA or less. [Refer to 2.6.2 for detail]
Note 4 Connect the temperature sensor contact when external regenerative resistor units are
connected.
2.2.3
Contact Output for
Drive Cutoff
(Note 3)
Circuit for Stop
PC Software Cable or Dummy plug
SIO connector
System I/O connector
Emergency
stop circuit
exclusive
use 24V
Emergency
stop switch
Short-circuit
in PC software cable
CR1
(Note 1)
Emergency
stop reset
switch
Motor power
supply
MC1
(Note 2)
Control power
supply
CR1
(Note 1)
AC power supply input connector
Temperature Sensor Contact for External
Regenerative Resistor Unit
(Note 4)
Summary of Contents for SCON-CB-F
Page 2: ......
Page 4: ......
Page 10: ......
Page 16: ......
Page 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Page 60: ...1 Specifications Check 44 ...
Page 266: ...3 Operation 250 ...
Page 276: ...4 Field Network 260 ...
Page 282: ...5 Vibration Suppress Control Function 266 ...
Page 362: ...9 Troubleshooting 346 ...
Page 444: ...10 Appendix 428 ...
Page 449: ......