3. Operation
160
3.2.2 Control of Input Signal
The input signal of this controller has the input time constant of 6ms considering the prevention
of wrong operation by chattering and noise.
Therefore, input each input signal for 6ms or more
(Note 1)
continuously. The signal cannot be
identified if it is less than 6ms.
Note 1 It is necessary to input 26ms or more for PWRT Signal of PIO Pattern 1.
[Refer to 3.2.4 Operation with Position No. Input = Operations of PIO Patterns 0 to 3 and 6.]
3.2.3 Operation Ready and Auxiliary Signals = Common to Patterns 0 to 7
[1] Emergency stop status (EMGS)
Output
PIO signal
*EMGS
Common to
Patterns 0 to 7
{
{
: Available,
×
: Unavailable
1) Emergency Stop Status EMGS is usually turned on and is turned off when “2.1.3 4)” is
open between EMG+ and EMG- (emergency stop condition or not connected).
2) It turns back ON if the emergency stop condition is released and the circuit is closed
between EMG+ and EMG-.
Have an appropriate safety treatment such as interlock with this signal for the host controller
(PLC, etc.).
(Note 1)
EMGS is different from the emergency stop output caused by a controller alarm.
Input Signal
Input Signal
Identify
Not Identify
6ms
Summary of Contents for SCON-CB-F
Page 2: ......
Page 4: ......
Page 10: ......
Page 16: ......
Page 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Page 60: ...1 Specifications Check 44 ...
Page 266: ...3 Operation 250 ...
Page 276: ...4 Field Network 260 ...
Page 282: ...5 Vibration Suppress Control Function 266 ...
Page 362: ...9 Troubleshooting 346 ...
Page 444: ...10 Appendix 428 ...
Page 449: ......