2. Wiring
106
4) Shut off the motor power externally by inputting the emergency stop with using two units of
controllers or more.
24V
Emergency stop
reset switch
Emergency stop
switch
Emergency stop switch
for the teaching pendant
CR1
(Note 1)
0V
MC1
CR1
CR1
S1
S2
S1
S2
1
5
8
5
8
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
EMG
A
EMG
B
CR1
(Note 1)
MC1
(Note 2)
AC100V
AC200V
System I/O
SIO connector
Emergency stop circuit
exclusive use 24V
SIO connector
connecter
System I/O
connecter
EMG+
EMG-
L1
L2
L1C
L2C
AC power supply
Motor power
cutoff relay
(Note 3)
(Note 3)
input connector
AC power supply
input connector
Motor
power supply
Control
power supply
CR1
(Note 1)
MC1
(Note 2)
AC100V
AC200V
EMG+
EMG-
L1
L2
L1C
L2C
(Note 4)
Note 1 The power rating of the motor power-off relay turning ON/OFF with contact CR1 is 24V
DC and 10mA or less.
Note 2 Connect such as a connector to L1/L2 terminals when cutting off the motor power source
externally.
(CB/LC Types are equipped with the drive cutoff relay mounted inside the controller.)
Note 3 CGB/LCG Types are not equipped with a relay to enable to automatically identify a
teaching tool was inserted and switch the wiring layout. (It does not get short-circuited
between S1 and S2 terminals even if not connected.)
The controller on CB/LC Types automatically identifies that a teaching tool was inserted.
(When there is nothing plugged in, S1 and S2 are short-circuited inside the controller.)
Note 4 Since there is no motor power cutoff relay in CGB/LCG Types, make sure to establish a
cutoff relay externally.
2.4.3
Summary of Contents for SCON-CB-F
Page 2: ......
Page 4: ......
Page 10: ......
Page 16: ......
Page 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Page 60: ...1 Specifications Check 44 ...
Page 266: ...3 Operation 250 ...
Page 276: ...4 Field Network 260 ...
Page 282: ...5 Vibration Suppress Control Function 266 ...
Page 362: ...9 Troubleshooting 346 ...
Page 444: ...10 Appendix 428 ...
Page 449: ......