10. Appendix
348
10.1.2 Detailed Connection Diagram of Communication Lines
SIO Converter
4-way Junction (Manufactured by : 5-1473574-4)
(SGA) A
(SGB) B
0V
1
2
3
1
2
7
1
2
7
1
2
3
1
2
3
4
1
2
3
4
1
2
3
4
Personal
Computer
Touch Panel Teaching
or
Teaching Pendant
J4, J5
Mini DIN
8 pin
Double Shield Cable
(Note 1)
Recommended : Taiyo Cabletec Corp.
HK-SB/20276XL
(AWG22)
e-CON Connector
(Manufactured by : 4-1473562-4)
Cover Color : GN
Controller
Link Cable
CB-RCB-CTL002
SCON 2nd Unit
SIO Connector
SIO Connector
Class D grounding
SCON 1st Unit
e-CON Connector
(Manufactured by : 4-1473562-4)
Housing Color : GN
e-CON Connector
(Manufactured by : 3-1473562-4)
Cover Color : OR
Controller
Link Cable
CB-RCB-CTL002
YW
OR
BL
YW
OR
BL
SGA
SGB
GND
SGA
SGB
GND
(A)
(B)
SGA
SGB
0V
Shield
(Note 1) Apply a 2-pair shielded cable.
When connecting a cable other than recommended to (A) and (B), make sure to use a
vinyl cable dedicated for control devices with the sheath outer diameter from 1.35 to
1.60mm. Using cables with outer diameter out of the specification may cause poor
contact to occur.
Caution : When cables with outer diameter out of the specification are used, use a
terminal block instead of 4-direction junction. In this configuration, disconnect
the e-CON connector of the link cable. If an error possibly caused by poor
contact occurs frequently, replace the junction with the terminal block.
Summary of Contents for SCON-CB-F
Page 2: ......
Page 4: ......
Page 10: ......
Page 16: ......
Page 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Page 60: ...1 Specifications Check 44 ...
Page 266: ...3 Operation 250 ...
Page 276: ...4 Field Network 260 ...
Page 282: ...5 Vibration Suppress Control Function 266 ...
Page 362: ...9 Troubleshooting 346 ...
Page 444: ...10 Appendix 428 ...
Page 449: ......