8. Parameter
315
[109] Home preset value (Parameter No.139)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
139 Home preset value
PRST
mm
-9999.99 to
9999.99
In accordance
with actuator
For the actuator of absolute specification, set this parameter so that (home return value
of this parameter) is within the range between 0 and the ball screw lead.(as it is necessary to
register the Z-phase nearest to the mechanical end as the datum)
The value should be an integer multiple of ±(ball screw lead length) including 0.00.
(If the home return offset is within the range between 0 and ball screw lead length, the value of
this parameter is 0.00.)
Also, when a value other than 0.00 is set in this parameter, home-return complete position
cannot be 0.00, and it gets to the positon of home po this parameter.
For the actuator of incremental specification, always set this parameter to 0.00.
<Setting example 1>
With ball screw lead length 4mm and home return offset level 10mm, set this parameter to
-8mm.
Caution: If the above condition is not satisfied, the home position at restart after home
return may shift by an integer multiple of the ball screw lead.
Home Return Offset Level (10mm)
Home position preset value (-8mm)
Home return
completion position
[-8mm]
Ball Screw Lead Length (4mm)
Ball Screw Lead Length (4mm) Ball Screw Lead Length (4mm)
Home Position
[0mm]
Summary of Contents for SCON-CB-F
Page 2: ......
Page 4: ......
Page 10: ......
Page 16: ......
Page 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Page 60: ...1 Specifications Check 44 ...
Page 266: ...3 Operation 250 ...
Page 276: ...4 Field Network 260 ...
Page 282: ...5 Vibration Suppress Control Function 266 ...
Page 362: ...9 Troubleshooting 346 ...
Page 444: ...10 Appendix 428 ...
Page 449: ......