9. T
roubleshooting
337
Alarm
Code
Alarm
Level
Alarm Name
Cause/Treatment
0A6
Cold start
Dynamic brake not
released
Cause
: The dynamic brake cannot be released when the
servo is ON due to noise and electrostatic, etc.
Treatment : Implement measures to eliminate noise or
electrostatic.
There is a concern of circuit breakdown. Please
contact IAI.
0A7
Operation
release
Command deceleration
error
Cause
: Because there is not enough deceleration distance
when the deceleration is changed to a lower setting
during the operation, the actuator exceeded the soft
limit when deceleration was made from the current
position with the deceleration after the change.
Soft limit
Deceleration starting position
not resulting in soft limit overshoot
If a command is issued here,
soft limit overshoot will occur.
The cause is that the timing to make the next
movement command when the speed was changed
during the operation was late.
Treatment : Make the timing earlier for the movement command
for the deceleration speed change.
0A8
Unsupported
motor/encoder types
Cause
: The motor connected to the controller is not
applicable or the type of the encoder that the motor
is connected is not applicable.
Treatment : Please contact us if the alarm is issued even with
the applicable actuator and the same problem
happens again even after rebooting the power.
0A9
Loadcell data error
Cause
: The data acquired from loadcell at power-on or
software reset is incorrect.
Treatment : 1) Effect of noise is suspected. Check if there is a
device radiating the noise and have a treatment
to prevent receiving the noise.
2) The loadcell may be faulty. If the error keeps
occurring even with the power reboot for several
times, it is considered the loadcell is
malfunctioned. Please contact IAI.
0B3
Spurious absolute error
Cause
: Home-return operation was not performed properly.
1) Work is interfering with peripheral equipment in
the middle of home return.
2) Encoder Error
Treatment : 1) Remove the interference.
2) Please contact IAI.
0B4
Cold start
Electric angling
mismatching
Cause
: This alarm indicates that the position deviation
counter has overflowed.
Treatment : The alarm occurs when the actuator cannot be
operated.
Confirm about the load conditions, that the work
does not interfere with any object nearby or the
brake has been released, etc.
If the error occurs even when the servo is ON, the
cable breakage or disconnection is considered.
Check the cable connection. Please contact IAI if
there is no failure in the cable and connector
connections.
0B5
Operation
release
Z-Phase position error
The position where the Z-phase is detected before the home
return operation, is out of the specified range.
Cause
: Encoder Error
Treatment : Please contact IAI.
Summary of Contents for SCON-CB-F
Page 2: ......
Page 4: ......
Page 10: ......
Page 16: ......
Page 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Page 60: ...1 Specifications Check 44 ...
Page 266: ...3 Operation 250 ...
Page 276: ...4 Field Network 260 ...
Page 282: ...5 Vibration Suppress Control Function 266 ...
Page 362: ...9 Troubleshooting 346 ...
Page 444: ...10 Appendix 428 ...
Page 449: ......