PNEUMATIC CONTROL FUNDAMENTALS
83
ENGINEERING MANUAL OF AUTOMATIC CONTROL
M
M B
P/E RELAY
TEMPERATURE
CONTROLLER
BELLOWS
SPRING
SETPOINT
ADJUSTMENT
PUMP
PUMP
VOLTAGE
N.O.
N.C.
C
C2384
Fig. 52. P/E Relay Application.
ELECTRONIC-PNEUMATIC TRANSDUCER
The electronic-pneumatic transducer is a proportional relay
that varies the branch air pressure linearly 3 to 15 psi in
response to changes in an electrical input of 2 to 10 volts or 4
to 20 ma. Electronic-pneumatic transducers are used as the
interface between electronic, digital, or computer-based control
systems and pneumatic output devices (e.g., actuators).
Figure 53 shows discharge air temperature control of a
heating coil using digital control for sensing and control. The
output of the transducer positions the valve on a heating coil.
M B
M
HEATING
VALVE
DISCHARGE
AIR
HEATING COIL
ELECTRONIC-
PNEUMATIC
TRANSDUCER
DDC
CONTROLLER
ELECTRONIC
TEMPERATURE
SENSOR
C2378
A resistance-type temperature sensor in the discharge air
duct is the input to the controller, which provides all of the
system adjustments and logic requirements for control. The
controller output of 2 to 10 volts dc is input to the electronic-
pneumatic transducer, which converts the signal to a 3 to 15
psi output to position the heating valve.
PNEUMATIC SWITCH
The pneumatic switch is available in two- or three-position
models (Fig. 54). Rotating the switch knob causes the ports to
align in one of two ways in a two-position switch, and in one
of three ways in a three-position switch. The two-position
switch is used for circuit interchange. The three-position switch
sequentially switches the common port (Port 2) to the other
ports and blocks the disconnected ports.
Fig. 53. Typical Electronic-Pneumatic
Transducer Application.
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
THREE-POSITION SWITCH
TWO-POSITION SWITCH
C1887
Fig. 54. Pneumatic Switches.
Figure 55 shows a typical application for sequential
switching. In the OPEN position, the valve actuator exhausts
through Port 4 and the valve opens. In the AUTO position, the
actuator connects to the thermostat and the valve is in the
automatic mode. In the CLOSED position, the actuator
connects to main air and the valve closes.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...