ENGINEERING MANULA OF AUTOMATIC CONTROL
INDIVIDUAL ROOM CONTROL APPLICATIONS
417
Fig. 23. Unit Ventilator in Standby/Warm-up Stage.
CYCLE I–FIXED MAXIMUM PERCENTAGE OF OUTDOOR AIR
When the space is warmed to the low end of the thermostat
throttling range, Cycle I begins. As shown in Figure 24, control
components are the room thermostat, heating coil valve, damper,
and modulating low-limit controller. The outdoor air damper
and heating coil valve operate in sequence in accordance with
the demand of the thermostat. The heating valve is full open.
As space temperature rises, the thermostat modulates the
damper to its maximum open position. The fixed maximum
position is normally 100 percent open. As space temperature
continues to rise, and after the damper moves to its maximum
position, the heating coil valve modulates closed. If a cooling
coil is installed in the unit, the cooling coil valve opens as space
temperature rises further. The low limit controller is necessary
to prevent freezing conditions that occur when occupants lower
the room control setpoint when it is below freezing outside,
plus it prevents the discomfort that would result in discharging
air into the room below 55 degrees F.
Fig. 24. Unit Ventilator Cycle I Control.
CYCLE II–FIXED MINIMUM PERCENTAGE OF OUTDOOR AIR
Cycle II control (Fig. 25) provides a fixed minimum
percentage of outdoor air (usually 10 to 33 percent, adjustable
from 0 to 100 percent).
At low space temperatures, the outdoor air damper is closed
and the heating coil valve and face damper are full open. As
space temperature rises, the outdoor air damper moves to its
minimum position. On a further rise in space temperature, the
face damper modulates closed, and on a further rise in space
temperature, the coil valve closes. When the space temperature
is at setpoint, the valve is full closed. As space temperature
rises above setpoint, the outdoor and return air dampers
modulate to 100 percent outdoor air at the top of the throttling
range. The low-limit controller can limit the closure of the coil
valve, face damper, and the opening of the outdoor air damper
to prevent the discharge air temperature from dropping below
its setpoint.
C3040
CONVECTION
AIR
OUTDOOR
AIR
OA, RA
DAMPERS
OPEN
CLOSED
RETURN
AIR
FILTER
HEATING
COIL
VALVE
FAN
FAN
INTERLOCK
THERMOSTAT
DAMPER
ACTUATOR
C3029
DISCHARGE
AIR
OUTDOOR
AIR
OPEN
OA, RA
DAMPERS
RETURN
AIR
FILTER
HEATING
COIL
VALVE
FAN
FAN
INTERLOCK
LOW-LIMIT
TEMPERATURE
CONTROLLER
THERMOSTAT
DAMPER
ACTUATOR
OPERATION CYCLE
HEATING
VALVE
OUTDOOR
AIR
DAMPER
FINAL
CONTROL
ELEMENT
POSITION
CLOSED
LOW
SPACE TEMPERATURE
HIGH
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...