![Honeywell AUTOMATIC CONTROL Engineering Manual Download Page 125](http://html.mh-extra.com/html/honeywell/automatic-control/automatic-control_engineering-manual_149859125.webp)
ENGINEERING MANUAL OF AUTOMATION CONTROL
ELECTRIC CONTROL FUNDAMENTALS
115
TRANSFORMER
STOP
START
OL
M
C2538
STARTER
FUSED
DISCONNECT
1M
OL
T1
2M
3M
4M
OL
OL
T2
T3
L3
L2
L1
F
F
F
F
MOTOR
TRANSFORMER
OFF
HAND
OL
M
C2539
STARTER
FUSED
DISCONNECT
1M
OL
T1
2M
3M
AUTO
OPERATING CONTROL
DEVICE
OL
OL
T2
T3
L3
L2
L1
F
F
F
F
MOTOR
OPERATION
Three basic types of motor control circuits are discussed in
the following. This topic is only intended to illustrate general
principles. There are many variations for each of these of circuits.
MOMENTARY START-STOP CIRCUIT
Figure 35 illustrates a momentary push-button start-stop
circuit. Both the START and the STOP buttons are spring loaded
and return to the positions shown after pressing momentarily.
Pressing the START button completes a circuit energizing starter
solenoid M. Contacts 1M through 3M start the motor and
contact 4M forms a holding circuit across the START button
allowing it to be released. Pressing the STOP button opens the
holding circuit, drops out the starter coil M, and stops the motor.
For digital control N.C. and N.O. momentarily actuated relay
contacts under computer control are added to the start and stop
contacts circuit. The N.C. contact is in series with the stop
contact and the N.O. contact is in parallel with the start contact.
An overload in any of the motor coils causes the associated
overloads OL to heat up and open the OL contacts, opening the
holding circuit, and stopping the motor. Overloads are thermal
heaters which allow brief periods of significant overload but
their response is too slow to protect the electrical system from
a short circuit. The circuit shown includes a separate manually
operated, fused (F), line disconnect, for short circuit protection.
Fig. 36. Hand-Off-Auto Start-Stop Circuit.
HAND-OFF-AUTO START-STOP CIRCUIT
The starter switch in Figure 36 has three positions: HAND,
OFF, and AUTO. The HAND position energizes starter solenoid
M and starts the motor. The OFF position deenergizes starter
solenoid M and stops the motor. The AUTO position allows the
motor to be turned on or off as called for by an operating control
device (interlock) such as a thermostat, pressure controller, or
relay contact. This is the preferred starter circuit when the motor
load is under automatic control.
Fig. 35. Momentary Push-button Start-Stop Circuit.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...