ENGINEERING MANUAL OF AUTOMATIC CONTROL
SMOKE MANAGEMENT FUNDAMENTALS
175
∆
P = Pressure difference, in. wc
Fig. 2. Smoke Movement Caused by Normal or Reverse
Stack Effect.
When it is colder inside than outside, there is a movement of
air downward within the building. This is called reverse stack
effect. With reverse stack effect, air enters the building above
the neutral plane and exits below the neutral plane.
The pressure difference across the building’s exterior wall
caused by temperature differences (normal or reverse stack
effect) according to Design of Smoke Management Systems
for Buildings published by ASHRAE is expressed as:
3
Where:
Ks = Coefficient, 7.64
To = Absolute temperature of outdoor air,
Rankine (R)
Ti = Absolute temperature of air inside the shaft,
Rankine (R)
h = Distance from the neutral plane, ft
BUOYANCY
Buoyancy is the tendency of warm air or smoke to rise when
located in cool surrounding air. Buoyancy occurs because the
warmer air is less dense than the cooler air, resulting in pressure
differences. Large pressure differences are possible in tall fire
compartments.
— Underwriters Laboratories (UL) Standards:
–
UL 555, Standard for Fire Dampers and
Ceiling Dampers
REGISTER
CORRIDOR
M13022
STAIRCASE
BUILDING
STACK
BUILDING
SPACE
WIND
MECHANICAL
HVAC
SYSTEM
GAS
EXPANDS
BUOYANT SMOKE
C5153
NEUTRAL
PLANE
REVERSE STACK EFFECT
NORMAL STACK EFFECT
NOTE: ARROWS INDICATE DIRECTION OF AIR MOVEMENT
–
UL 555S, Standard for Leakage Rated Dampers
for Use In Smoke Control Systems
–
UL 864, Standard for Control Units for Fire–
Protective Signaling Systems (UL Category UUKL)
DESIGN PRINCIPLES
CAUSES OF SMOKE MOVEMENT
The movement or flow of smoke in a building is caused by a
combination of stack effect, buoyancy, expansion, wind velocity,
and the HVAC system. See Figure 1. These items basically cause
pressure differences resulting in movement of the air and smoke
in a building.
Fig. 1. Factors Affecting the Movement of Smoke.
Before controls can be applied, it is necessary to first
understand the overall movement of smoke.
STACK EFFECT
Stack effect is caused by the indoor and outdoor air
temperature differences. The temperature difference causes a
difference in the density of the air inside and outside of the
building. This creates a pressure difference which can cause a
vertical movement of the air within the building. This
phenomenon is called stack effect. The air can move through
elevator shafts, stairwells, mechanical shafts, and other vertical
openings. The temperature-pressure difference is greater for
fire-heated air which may containing smoke than it is for normal
conditioned air. For further information on stack effect refer to
the Building Airflow System Control Applications section.
When it is colder outside than inside, there is a movement of
air upward within the building. This is called normal stack effect.
Stack effect is greater for a tall building than for a low building;
however, stack effect can exist in a one-story building. With
normal stack effect, air enters the building below the neutral
plane, approximately midheight, and exits above the neutral
plane. See Figure 2. Air neither enters nor exits at the neutral
plane, a level where the pressures are equal inside and outside
the building.
∆
P = K s x
(
)
1
To
–
1
Ti
x h
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...