ENGINEERING MANUAL OF AUTOMATION CONTROL
BUILDING AIRFLOW SYSTEM CONTROL APPLICATIONS
285
C2633
OA
RELIEF
FAN
RA
MIXED AIR
TEMPERATURE
CONTROLLER
STATIC
PRESSURE
CONTROLLERS
OUTDOOR
STATIC
PRESSURE
BUILDING
SPACE
STATIC
PRESSURE
SELECTOR
SUPPLY
FAN
RETURN DAMPER CONTROL FOR VAV SYSTEMS
In systems having a return fan, when the mixed air control
cycle is not operating, the outdoor air (or maximum outdoor
air) and relief dampers are closed and the return damper remains
fully open. When the mixed air control cycle is operating, the
return damper modulates closed and outdoor air (or maximum
outdoor air) and relief dampers modulate open. The return
damper should be sized for twice the pressure drop of the
outdoor air (or maximum outdoor air) and relief dampers. This
prevents the possibility of drawing outdoor air through the relief
damper (Fig. 34).
C2630
OA
FLOW
MEASURING
STATION
FLOW
MEASURING
STATION
AIRFLOW
CONTROLLER
AIRFLOW
CONTROLLER
A. FLOW MEASURING STATION IN OUTDOOR AIR DUCT
OA
B. FLOW MEASURING STATIONS IN SUPPLY AND RETURN DUCTS
RETURN
AIR
DAMPER
SUPPLY
FAN
Fig. 34. Return Air Damper Mixed Air Control Cycle.
In systems not having a return air fan, the return damper
controls minimum outdoor airflow or building pressurization.
Airflow tracking or direct building static pressure control can
be used to control the return damper, depending on which
parameter is most important. See Figure 35 for airflow tracking
and Figure 36 for direct building static pressure control.
C2631
STATIC PRESSURE
CONTROLLER
BUILDING SPACE
STATIC PRESSURE
OUTDOOR STATIC
PRESSURE
OA
SUPPLY
FAN
OA
RELIEF
FAN
RA
MIXED AIR
TEMPERATURE
CONTROLLER
AIRFLOW
CONTROLLERS
SELECTOR
C2632
FLOW
MEASURING
STATION
FLOW
MEASURING
STATION
SUPPLY
FAN
Fig. 36. Return Damper Control Using
Direct Building Static Pressure.
If a mixed air control cycle is required, a relief fan may be
required. In airflow tracking (Fig. 37), the mixed air controller
opens the outdoor air damper above minimum and the relief
fan tracks the outdoor air. In direct building static pressure
control (Fig. 38) the mixed air controller opens the outdoor air
and relief dampers and closes the return damper, causing the
relief fan to eliminate excessive pressure.
Fig. 37. Mixed Air Control Cycle with Relief
Fan Control Using Airflow Tracking.
C2629
RETURN
FAN
RA
OA
RETURN
AIR
DAMPER
SUPPLY
FAN
RELIEF
DAMPER
OUTDOOR
AIR
DAMPER
MIXED AIR
TEMPERATURE
CONTROLLER
Fig. 38. Mixed Air Control Cycle with Relief Fan Control
Using Direct Building Static Pressure.
Fig. 35. Return Damper Control Using Airflow Tracking.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...