PSYCHROMETRIC CHART FUNDAMENTALS
49
ENGINEERING MANUAL OF AUTOMATIC CONTROL
This converts to:
0.848 x 60 minutes = 50.9 gallons per hour
Recalling that the steam added 11.6 Btu per pound of dry air,
the total heat added is:
714.3 x 11.6 = 8286 Btu per minute
This converts to:
8286 x 60 minutes = 497,160 Btu per hour
Summarized, a steam humidifier always adds a little sensible
heat to the air, and the Process Line B–C angles to the right of
the 90F starting dry-bulb line because of the added sensible
heat. When the process line crosses the moisture content lines
along a constant dry-bulb line, only latent heat is added. When
it parallels a constant, horizontal moisture line, only sensible
heat is added.
AIR WASHERS
Air washers are also used as humidifiers particularly for
applications requiring added moisture and not much heat as in
warm southwestern climates. A washer can be recirculating as
shown in Figure 19 or heated as shown in Figure 20. In
recirculating washers, the heat necessary to vaporize the water
is sensible heat changed to latent heat which causes the dry-
bulb temperature to drop. The process line tracks the constant
enthalpy line because no total heat is added or subtracted. This
process is called “adiabatic” and is illustrated by Figure 21.
Point A is the entering condition of the air, Point B is the final
condition, and Point C is the temperature of the water. Since
the water is recirculating, the water temperature becomes the
same as the wet-bulb temperature of the air.
Fig. 21.
The next two psychrometric charts (Fig. 22 and 23) illustrate
the humidifying process using a heated air washer. The
temperature to which the water is heated is determined by the
amount of moisture required for the process. Figure 22 shows
what happens when the washer water is heated above the air
dry-bulb temperature shown at Point A. The temperature of
the water located at Point B on the saturation curve causes the
system air temperature to settle out at Point D. The actual
location of Point D depends upon the construction and
characteristics of the washer.
As the humidity demand reduces, the water temperature
moves down the saturation curve as it surrenders heat to the
air. This causes the water temperature to settle out at a point
such as Point C. The final air temperature is at Point E. Note
that the final air temperature is above the initial dry-bulb
temperature so both sensible and latent heat have been added
to the air.
C2598
PUMP
SUPPLY FAN
Fig. 19. Recirculating Air Washer.
C2599
PUMP
HEAT EXCHANGER
HWS
HWR
SUPPLY FAN
Fig. 20. Heated Air Washer.
A
B
C
D
SATURATION
CURVE
C1844
E
Fig. 22.
C1843
C
A
CONSTANT
ENTHALPY
LINE
B
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...