ENGINEERING CMANUAL OF AUTOMATION CONTROL
AIR HANDLING SYSTEM CONTROL APPLICATIONS
237
CONDITION FOR SUCCESSFUL OPERATION
The water must be supplied at a reasonably constant pressure.
LIMITATIONS
Modulating water flow through a constant air volume chilled
water coil usually causes a rise in space RH because the coil
leaving water temperature rises significantly.
SPECIFICATIONS
The flow of chilled water through the cooling coil shall be
controlled by a three-way valve modulated by a space
temperature PI control loop. The valve shall close to the coil
upon fan shutdown and open to the coil upon loss of actuator
motive force.
PSYCHROMETRIC ASPECTS
The temperature, and often moisture content, of leaving air
increases as the sensible cooling load lightens.
In the following chart it is assumed that:
1. Desired space and RA condition is 78
°
F DB and 50%
RH (65
°
F WB).
2. Design OA temperature is 95
°
F DB and 75
°
F WB.
3. Air entering the system is from the ECONOMIZER
CYCLE DECISION application. This system operates
on 35 percent OA during the cooling cycle.
4. Coil discharge temperature is 55
°
F.
C2558-2
OA 95
°
F DB,
75
°
F WB
RA 78
°
F DB,
50% RH
SA 55
°
F DB
2
1
MA
TWO-POSITION CONTROL OF DIRECT EXPANSION COIL SYSTEM
Functional Description
The following results are obtained:
Item
No.
Explanation
1
Mixed air temperature at cooling design
condition.
2
Air entering the coil is cooled along a line of
constant moisture content until saturation is
approached. Near saturation the moisture
content is reduced as the air is cooled. This
process involves both latent and sensible
cooling.
NOTE: Condition of coil leaving air will change with the
cooling load in the space. As the cooling load
decreases, the three-way valve will provide less chilled
water flow to the coil and the discharge air temperature
will rise (approximately along Line 2).
M10470
4
MA
SA
ON
1
8
8
10
MINIMUM
ON TIME
MINIMUM
OFF TIME
COMPRESSOR
(MINUTES)
6
9
5
RELAY
RELAY
OPEN
CONTROL
PROGRAM
3
7
2
76
2.5
76
SUPPLY
FAN
TEMPERATURE CONTROL
DIFFERENTIAL (DEGREES)
TO COMPRESSOR
START CIRCUIT
COMPRESSOR
VOLTAGE MONITOR
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...