PNEUMATIC CONTROL FUNDAMENTALS
75
ENGINEERING MANUAL OF AUTOMATIC CONTROL
provide a simple form of sequence control (e.g., operating
heating and cooling valves from a single thermostat). Typical
spring pressure ranges are 2-7 psi, 8-12 psi, and 3-13 psi.
CONTROL VALVES
Single-seated globe valves (Fig. 28) are used where tight
close-off is required. The valve body can be either direct acting
or reverse acting. A direct-acting valve body allows flow with
the stem up, while a reverse-acting valve body shuts off flow
with the stem up. The combination of valve body and actuator
(called the valve assembly) determines the normal valve stem
position.
Fig. 28. Single-Seated Valves.
The position maintained by the valve stem depends on the
balance of forces acting on it:
— Force F1 from the air pressure on the diaphragm
— Opposing force F2 from the actuator spring
— Controlled-medium force F3 acting on the valve disc and
plug due to the difference between inlet and outlet
pressures
An increase in controller branchline pressure increases force
F1, (Fig. 28A), moving the diaphragm down and positions
the valve stem toward closed until it has moved far enough
that the sum of the spring force F2 and the controlled-medium
force F3 increases balance the increased force F1 on the
diaphragm. Conversely, a decrease in controller branchline air
pressure in the diaphragm chamber of a direct-acting actuator
decreases force F1, allowing forces F2 and F3 to push the
diaphragm upward and move the valve stem toward the open
position.
In Figure 28B, branchline pressure is applied on the bottom
surface of the diaphragm. An increase in air pressure in the
diaphragm chamber increases force F1 causing the actuator
diaphragm to move upward and open the valve. Motion
continues until the increase in pressure on the diaphragm plus
the controlled-medium force F3 is balanced by the increase in
spring compression (force F2). On a decrease in air pressure
in the diaphragm chamber, the compressed spring moves the
diaphragm down toward its normal position and the valve stem
toward closed. A normally closed valve assembly usually has
a lower close-off rating against the pressure of the controlled
medium than a normally open valve because the spring force
F2 is the only force available to close the valve.
In Figure 28C, an increase in branchline pressure in the
actuator increases force F1 causing the diaphragm to move
downward and open the valve. Motion continues until the
increase in pressure on the diaphragm (force F1) plus the
controlled-medium force F3 is balanced by the increase in
spring compression (force F2). On a decrease in air pressure
in the diaphragm chamber, the compressed-spring pressure
moves the diaphragm up and the valve stem moves toward
the closed position.
In a double-seated valve (Fig. 29), the controlled agent flows
between the two seats. This placement balances the inlet
pressures between the two discs of the plug assembly and
reduces the actuator force needed to position the plug assembly.
Double-seated valves generally do not provide tight close-off
because one disc may seat before the other and prevent the
other disc from seating tightly.
BRANCH
LINE
FLOW
NORMALLY OPEN VALVE ASSEMBLY (DIRECT-ACTING
VALVE BODY AND DIRECT-ACTING ACTUATOR)
C2613
F1
F2
F3
BRANCH
LINE
FLOW
NORMALLY CLOSED VALVE ASSEMBLY (DIRECT-ACTING
VALVE BODY AND REVERSE-ACTING ACTUATOR)
F1
(F2
F3
)
BRANCH
LINE
FLOW
NORMALLY CLOSED VALVE ASSEMBLY (REVERSE-ACTING
VALVE BODY AND DIRECT-ACTING ACTUATOR)
F1
F2
F3
A.
B.
C.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...