LOW-LIMIT CONTROL
A low-limit controller is connected in parallel with the
thermostat as shown in Figure 9. The low-limit controller can
complete the circuit to the valve actuator even though the
thermostat has opened the circuit. The actuator remains
energized when the contacts on either controller are closed.
Fig. 9. Series 40 Control System with Low Limit.
SERIES 80 CONTROL CIRCUITS
APPLICATION
Series 80 is the low-voltage equivalent of Series 40. It is
suited for applications requiring low-voltage, two-position
control of two-wire circuits by single-pole, single-throw
controllers.
Series 80 has two advantages over Series 40:
1. Since contacts of Series 80 controllers are required to
carry less current, the controller mechanism can be
physically smaller than a Series 40. The controller there-
fore has less lag and the capability to have a narrower
differential.
2. Low-voltage wiring (when not in conduit or armor) costs
less than line-voltage wiring.
EQUIPMENT
CONTROLLERS
1. Temperature controllers.
2. Humidity controllers.
3. Any low-voltage device with a minimum of one
normally-open contact such as a low-voltage relay.
A Series 80 controller cannot switch line voltage directly. A
relay must be used between the controller and a line-voltage
load. However, Series 40 or Series 80 controllers can be used
with Series 80 actuators.
A Series 80 controller has snap-acting contacts or a mercury
switch. Some Series 80 controllers are three-wire, double-throw
devices as in heating-cooling thermostats.
Many Series 80 heating thermostats have internal adjustable
heaters in series with the load. This provides enough artificial
heat during the on cycle to cause the sensing element to open
the switch on a smaller rise in space temperature. Some Series
80 cooling thermostats have a fixed heater which energizes when
the cooling circuit is deenergized. This provides artificial heat
to the sensing element to close the switch on a small rise in
space temperature. This cooling and heating anticipation (also
called time proportioning) provides close space-temperature
control. See the Control Fundamentals section.
RELAYS AND ACTUATORS
Relays and actuators are similar to those of Series 40 except
that they operate on low voltage.
OPERATION
Figure 10 illustrates a simple Series 80 circuit. This is the
same as a Series 40 circuit with the added transformer.
Fig. 10. Series 80 Actuator Application.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...