ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
317
THERMAL STORAGE CONTROL
GENERAL
Thermal storage is used to save heating or cooling for future
use. Typically enough storage is provided to meet the load
requirements for a 24-hour period. During the cooling season,
storage of low cost night time cooling can save energy and
demand charges and reduce the chilled water generating
equipment design size. During the heating season, storage of
rejected day time excess refrigeration heat or solar heat can be
used for night time heating loads. Storage may use a water
tank or ice bin for cooling and a water tank or thermal
conducting fluid for heat. The storage efficiency depends on
the amount of insulation and, in the case of water storage, on
minimizing the mixing of return water with storage water.
Mixing in water storage can be minimized by use of a segmented
container for storage (Fig. 24).
Primary control requirements are storage charge and storage
discharge at the proper times and rates. Storage charge, storage
discharge, and instantaneous cooling are the three basic control
modes. Combinations of the basic control modes may be
required to meet the load or predicted load. When the predicted
load is high, the chiller provides chilled water for both the
current load and for storage. When the predicted load occurs,
the stored cooling is added to the chiller output.
CONTROL MODES
The appropriate control mode depends on the load predicted
for next day, relative storage size, and relative costs of stored
and instantaneous cooling, including electrical demand rate
structures. The storage charging cycle is normally activated
when cooling generation cost is lowest, such as at night when
lower condenser water temperatures provide lower refrigeration
head and when lower time-of-day electric rates may be
applicable. The rate of charge should satisfy storage quantity
requirements within the limits of the time available.
Use of stored energy verses instantaneous cooling energy is
prioritized. When enough stored energy is available to satisfy
the load through the peak demand period of the next day, only
stored energy is used (storage priority). In this case, the charging
cycle is scheduled to start when low cost cooling is available.
The charging cycle is stopped when storage is sufficient for the
next days load or when the storage capacity is filled. The storage
discharge cycle is controlled to meet load conditions. If storage
capacity is not large enough for the next day, the chiller
supplements the use of stored cooling, as necessary. The control
sequences for segmented chilled water storage (Fig. 24) are:
–
Instantaneous Cooling Cycle: Pump P1 is on and Pump
P2 is off. Valves VC and VD are closed. Valve VI is
controlled by
∆
P and T1 controls chiller.
–
Charging Cycle: Valves VD and VI are closed and VC
is controlled by T6 to maintain the flow rate at F1. Pump
P2 is off. T1 controls chiller capacity to maintain 40F
CHWS temperature. When the T5 (A through E)
location, representing the needs for the next day, reaches
40F, the charging cycle is stopped.
–
Charging plus Instantaneous Cooling Cycle: Charging
cycle continues while VI is controlled from
∆
P. Pump
P2 is off. The flow through the storage is T5E to T5A.
–
Discharge Cycle (enough storage for anticipated load):
Valves VC and VI are closed, chiller and Pump P1 are off,
and Pump P2 is on. Valve VD is controlled from
∆
P.
–
Discharge plus Instantaneous Cooling Cycle (not
enough storage for anticipated load): Pumps P1 and P2
are on, VC is closed. Chiller demand D1 limits chiller
capacity while T2 positions VI to maintain chilled water
supply temperature.
∆
P throttles valve VD to provide
flow from storage.
Fig. 24. Segmented Chilled Water Storage.
The chiller takes priority when stored energy costs are larger
than instantaneous energy costs. Under these conditions the
only cooling stored is that required to reduce the anticipated
demand limit for the next day. Storage size and energy cost,
including demand charges, establish the control strategies for
this situation. The control objectives are to limit demand for
the billing period and to minimize energy costs. Chiller
discharge is controlled to meet load. The sequence of the control
is to run the charging plus instantaneous cooling cycle, then
stop charging when the quantity necessary to meet the
anticipated demand limit for the next day is stored.
CHILLER
D1
F1
T
5A
T
5B
T
5C
T
5D
T
5E
T
6
LOADS
VC
P1
T1
N.O.
N.O
.
N.O
.
P2
T2
∆
P
SEGMENTED STORAGE
C
C
C
D
D
D
VD
VI
I
= FLOW DIRECTION
C = CHARGING CYCLE
D = DISCHARGING CYCLE
I = INSTANTANEOUS COOLING
NOTE: NOT ALL CONTROLS ACTIVE FOR ALL SEQUENCES
C2693
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...