ENGINEERING MANUAL OF AUTOMATION CONTROL
BUILDING AIRFLOW SYSTEM CONTROL APPLICATIONS
282
Fig. 24. Locating Duct Static Pressure Sensor for
Supply Fan Control.
A wide proportional band setting (10 times the maximum
duct static pressure at the fan discharge) on the fan control is a
good starting point and ensures stable fan operation. Integral
action is necessary to eliminate offset error caused by the wide
proportional band. Integral times should be short for quick
response. The use of inverse derivative, which essentially slows
system response, does not produce the combination of stability
and fast response attainable with wide proportional band and
integral control modes. (See the Control Fundamentals section
for more information on proportional band and integral action.)
Inlet vane dampers, variable pitch blades (vane axial fans),
or variable speed drives are used to modulate airflow (both
supply and return). Actuators may require positive positioning
to deal with nonlinear forces. Variable speed drives, especially
variable frequency, provide excellent fan modulation and control
as well as maximum efficiency.
DUCT STATIC
HIGH-LIMIT SENSOR
AIR TERMINAL
UNITS
C2620
SUPPLY
FAN
Duct Static High-Limit Control
High-limit control of the supply fan duct static should be
used to prevent damage to ducts, dampers, and air terminal
units (Fig. 25). Damage can occur when fire or smoke dampers
in the supply duct close or ducts are blocked, especially during
initial system start-up. Fan shut-down and controlling high-
limit are two techniques used to limit duct static. Both
techniques sense duct static at the supply fan discharge.
DUCT STATIC
PRESSURE SENSORS
C2621
SUPPLY
FAN
AIR TERMINAL UNITS
DUCT
STATIC
HIGH-LIMIT
SENSOR
SMOKE DAMPERS
SMOKE DAMPERS
DUCT STATIC
PRESSURE SENSORS
Fig. 25. Duct Static High-Limit Control.
Fan shut-down simply shuts down the fan system (supply
and return fans) when its setpoint is exceeded. High-limit control
requires a manual restart of the fans and should be a discrete
component separate from the supply fan primary control loop.
The fan shut-down technique is lowest in cost but should not
be used with smoke control systems where continued fan
operation is required.
A controlling high-limit application is used when the fan
system must continue to run if duct blockage occurs, but its
operation is limited to a maximum duct static. For example, a
fire or smoke damper in the supply duct closes causing the
primary duct static pressure sensor to detect no pressure. This
would result in maximum output of the supply fan and
dangerously high static pressure if the controlling high pressure
limit is not present. A controlling high-limit control will
modulate the fan to limit its output to the preset maximum duct
static (Fig. 26).
SUPPLY
FAN
SUPPLY
FAN
SUPPLY
FAN
A.
DUCT STATIC
PRESSURE SENSOR
DUCT STATIC
PRESSURE SENSOR
B.
DUCT STATIC
PRESSURE SENSOR
DUCT STATIC
PRESSURE SENSOR
AIR TERMINAL
UNITS
AIR TERMINAL
UNITS
AIR
TERMINAL UNITS
C2619
C.
Fig. 26. Controlling Static High-Limit.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...