![Honeywell AUTOMATIC CONTROL Engineering Manual Download Page 383](http://html.mh-extra.com/html/honeywell/automatic-control/automatic-control_engineering-manual_149859383.webp)
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
373
Low pressure steam systems operate on pressures ranging from
0 psig to 15 psig. The steam main pressures are usually under 10
psig and the returns are vented to the atmosphere. To maintain
the return main pressures at 0 psig, an air vent releases the air
from the system when steam is present and allows it to return to
the system when steam is not present. These vents do not allow
steam to escape. A sealed chamber (bellows) within the vent
contains a volatile liquid which vaporizes or condenses when
temperature changes. This causes the valve to close when steam
is present preventing the discharge of steam from the system.
Since all of the air in a steam system may not be forced out
through the radiator vents, it is necessary to provide auxiliary
vents at the ends of the steam mains and in the returns to ensure
air removal from the system. These vents are larger than radiator
vents and are referred to as quick vents.
VARIABLE VACUUM RETURN SYSTEMS
In a variable vacuum steam system, also called a
subatmospheric steam system, the operating pressures range
from 20 in. Hg vacuum to 15 psig. The principle of water boiling
at reduced temperatures in a vacuum is the basis of a variable
vacuum steam system. In an atmospheric-return low-pressure
steam system, when the thermostat turns the burner off, boiling
ceases as soon as the temperature of the water drops to 212F.
In a variable vacuum system, boiling continues until the water
temperature drops to the boiling point of the vacuum pressure
created by the condensation of steam in the system. This means
that steam is continuously supplied to the radiator at a decreasing
temperature until the limit of induced vacuum is reached. Table
7 shows reduced heat output from radiators in a vacuum system.
To operate successfully, the system must be air tight. Variable
vacuum systems use nonreturn vents which allow air to leave
the system but none to return. A nonreturn vent is similar to the
low pressure steam vent with a small check disc that closes to
prevent inflow of air to the system when the pressure drops
below atmospheric.
The period of time that a variable vacuum system can operate
in the vacuum range is dependent upon the tightness of the
connections of the system. Once a variable vacuum system has
built up a vacuum, it is possible for the burner to operate at
frequent enough intervals to keep the system within the vacuum
range during mild and intermediate load conditions. Since a
low steam temperature is maintained, the radiator temperature
is low. By keeping the radiator warm for longer periods of time,
temperature stratification in the space is reduced.
Table 7. Heat Output versus Steam Pressure for Radiators, Convectors, and Coils.
Saturated Steam
Pressure
Steam
BTU/HR/EDR
Typical Steam Coil
a
With 40F Entering Air
PSIG
Temp, ˚F
Radiators
b
Convectors
c
MBH
d
10
239.4
286
288
111.0
5
227.1
262
259
104.5
4
224.4
254
250
103.2
3
221.5
247
242
101.6
2
218.5
240
235
100.0
1
215.3
233
228
98.2
0
212.0
226
221
96.2
2 in. Hg
208.5
216
211
94.5
4 in. Hg
204.8
209
204
92.0
6 in. Hg
201.0
199
194
90.2
10 in. Hg
192.2
182
178
—
15 in. Hg
178.9
158
151
—
20 in. Hg
161.2
125
111
—
a 2 row steam distributing coil, 7 fins per inch, 500 fpm face velocity, and 2.4 sq ft face area
b 75F Room temperature
c 70F Inlet temperature
d 1000 Btu/hr
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...