ENGINEERING MANUAL OF AUTOMATIC CONTROL
SMOKE MANAGEMENT FUNDAMENTALS
179
Fig. 6. Typical Smoke Control System Meeting the Requirements of UL Standard 864 and NFPA 92A.
FAN
DAMPER
END
SWITCH
FIREFIGHTERS’
SMOKE CONTROL
STATION (FSCS)
REMOTE
CONTROL
PANEL 2
TO ADDITIONAL
REMOTE
CONTROL
PANELS
OPERATOR’S
CONSOLE
ALARM
PROCESSOR
COMMUNICTIONS
BUS
REMOTE
CONTROL
PANEL 1
INITIATING
PANEL
ALARM
DETECTORS
M13026
FLOW
SWITCH
SMOKE DETECTOR
(NFPA SYMBOL)
The following discussions cover smoke control applications
for building zones, stairwells, and large areas including malls
and atria. Each of these discussions conclude with a typical
operational sequence complying with UL Standard 864 for the
smoke control system illustrated in Figure 6.
Products utilized in smoke control and management systems
should be ULI labeled for the following applications:
— DDC Panels: Smoke Control Equipment.
— Building Management System/Fire Control System:
Critical Process Management, Smoke Control, or Fire
Control Unit Equipment
ZONE PRESSURIZATION CONTROL
The objective of zone pressurization is to limit the movement
of smoke outside the fire or the smoke control zone by providing
higher pressure areas adjacent to the smoke zone. Zone
pressurization can be accomplished by:
— Providing supply air to adjacent zones
— Shutting off all returns or exhausts to floors other than
the fire floor
— Exhausting the smoke zone (also aids stairwell
pressurization systems by minimizing buoyancy and
expansion effects)
— Shutting off, providing supply air to, or leaving under
temperature control all supplies other than those
adjacent to the fire floor
A smoke control zone can consist of one or more floors or a
portion of a floor. Figure 7 illustrates typical arrangements of
smoke control zones. The minus sign indicates the smoke zone.
The plus signs indicate pressurized nonsmoke zones. In the
event of a fire, the doors are closed to the fire or smoke control
zone and the adjacent zones are pressurized. In the example in
Figures 7A and 7B, the floors above and below the smoke zone
are pressurized. The application in Figure 7B is called a pressure
sandwich. In Figures 7C and 7D, the smoke zone consists of
more than one floor. In Figure 7E, the smoke zone is only a
part of a floor and all the rest of the building areas are
pressurized. Smoke zones should be kept as small as reasonable
so control response can be readily achieved and quantities of
air delivered to the nonsmoke zones can be held to manageable
levels.
+
+
+
–
+
+
+
+
+
+
+
+
C5154
(E)
+
+
+
+
+
+
SMOKE
ZONE
+
+
+
+
+
+
–
–
–
+
+
+
+
+
+
+
+
+
–
–
–
+
+
+
+
+
+
–
+
+
+
+
–
+
(C)
(D)
(A)
(B)
SMOKE
ZONE
SMOKE
ZONE
Fig. 7. Typical Zone Pressurization Arrangements for
Smoke Control Zones.
The practice of exhausting air as a means of providing higher
pressure areas adjacent to the smoke zone should be examined
carefully. Exhausting air from the fire floor may tend to pull
the fire along and cause flames to spread before they can be
extinguished.
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...