ENGINEERING CMANUAL OF AUTOMATION CONTROL
AIR HANDLING SYSTEM CONTROL APPLICATIONS
223
SPECIFICATIONS
See FAN SYSTEM START-STOP CONTROL
.
Anytime the supply fan runs, the OA, exhaust, and RA
dampers shall position to a minimum ventilation position and
shall be further modulated by an SA PID control loop to
maintain the SA temperature setpoint. The SA temperature
setpoint shall be varied from no less than 55
°
F to no more than
75
°
F as the space temperature PID loop cooling demand varies
from 100 to 0%. Anytime the economizer program is invoked,
the SA temperature control shall be enabled.
PSYCHROMETRIC ASPECTS
For the psychrometric aspects of this application, refer to
MIXED AIR CONTROL WITH ECONOMIZER CYCLE. The
psychrometric aspects of the two applications are the same.
HEATING CONTROL PROCESSES
M10458
6
CONTROL
PROGRAM
SA
N.O.
MA
ON
5
1
3
4
2
00
75
NORMAL
75
PERCENT
OPEN
Item
No.
Function
1-2
Control system energizes when fan is turned
on (See FAN SYSTEM START-STOP
CONTROL).
3,5
SA temperature maintained by modulating the
hot water valve.
4
Setpoint for SA temperature control.
6
Control program coordinates temperature
control and fan interlock.
FEATURES
1. Air is discharged at a minimum temperature.
2. Valve opens upon loss of motive force (electricity or
compressed air) and closes upon fan shutdown.
CONDITIONS FOR SUCCESSFUL OPERATION
1. A multiple inline coil arrangement should be used if a
high temperature rise is required.
2. Heating medium and flow must be available.
SPECIFICATIONS
See FAN SYSTEM START-STOP CONTROL
.
Anytime the supply fan runs, the hot water valve shall be
modulated by an SA PID control loop to maintain the SA
temperature setpoint. The hot water valve shall close upon fan
shutdown and open upon loss of motive force.
PSYCHROMETRIC ASPECTS
1. The SA temperature remains constant until the entering
air temperature exceeds the desired SA temperature.
2. In the following chart it is assumed that the SA PID
control loop is set at 75
°
F.
C2549-1
75
°
F COIL DISCHARGE
CONTROLLER SETPOINT
MA
1
The following results are obtained:
Item
No.
Explanation
1
Coil discharge is 75
°
F DB until MA exceeds
75
°
F DB, above which the coil valve is
closed, no heat is added, and SA condition is
equal to MA.
The following applications show various ways to control
heating in an air conditioning system.
CONTROL FROM SUPPLY AIR
Functional Description
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...