PNEUMATIC CONTROL FUNDAMENTALS
79
ENGINEERING MANUAL OF AUTOMATIC CONTROL
HIGH-PRESSURE SELECTOR RELAY
The high-pressure selector relay is a three-port relay that
transmits the higher of two input signals to the output branch.
The high sensitivity of the relay allows it to be used in sensor
lines with an accuracy of 2 to 3 degrees F.
The application shown in Figure 39 uses pressures from two
zones and a high-pressure selector relay to determine control.
A separate thermostat controls each zone damper. The
thermostat that calls for the most cooling (highest branchline
pressure) controls the cooling valve through the high-pressure
selector relay.
LOWEST
M
HIGHEST
1
2
3
N
LOAD ANALYZER RELAY
DA ZONE THERMOSTATS
TO
ZONE
DAMPERS
C2369
M B
M
M B
M
M B
M
M
M
M B
8-12 PSI
N.C. COOLING
VALVE
2-7 PSI
N.O. HEATING
VALVE
Fig. 39. Typical Application for
High-Pressure Selector Relay.
LOW-PRESSURE SELECTOR RELAY
The low-pressure selector relay is a three-port relay that
selects the lower of two input pressure signals and acts as a
repeater for the lower of the two inputs. The relay requires an
external restrictor on the input to the branch port. Figure 40
shows a low-pressure selector relay controlling the heating coil
valve from the thermostat that calls for the most heat.
Fig. 40. Typical Application for
Low-Pressure Selector Relay.
LOAD ANALYZER RELAY
The load analyzer relay is a bleed-type, diaphragm-logic
pressure selector. The relay selects the highest and lowest
branch pressure from multiple inputs to operate final control
elements (Fig. 41). The relay contains multiple diaphragms
and control nozzles. Each input pressure connects to two
diaphragms.
Fig. 41. Load Analyzer Relay in
Multizone Air Unit Application.
In Figure 41, the load analyzer relay selects the lowest
pressure signal from the thermostat in the coldest zone and
transmits that signal to a normally open heating valve. The
relay transmits the highest pressure signal from the thermostat
in the warmest zone to a normally closed cooling valve.
N.C. ZONE
DAMPER
2-7 PSI
DAMPER
ACTUATOR
HIGH-PRESSURE
SELECTOR RELAY
P1
P2
B
DA ZONE
THERMOSTAT
N.C. ZONE
DAMPER
2-7 PSI
DAMPER
ACTUATOR
8-12 PSI N.C.
COOLING COIL
VALVE
M
DA ZONE
THERMOSTAT
M B
C2363
M
M B
N.O. ZONE
DAMPER
8-12 PSI
DAMPER
ACTUATOR
LOW-PRESSURE
SELECTOR RELAY
P1
P2
B
N.O. ZONE
DAMPER
8-12 PSI DAMPER
ACTUATOR
RESTRICTOR
DA ZONE
THERMOSTAT
M B
2-7 PSI N.O.
HEATING COILVALVE
M
DA ZONE
THERMOSTAT
M B
C2364
EXH
M
Summary of Contents for AUTOMATIC CONTROL
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 11: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 1 CONTROL SYSTEMS FUNDMENTALS ...
Page 12: ......
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...PSYCHROMETRIC CHART FUNDAMENTALS 56 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATION CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 210: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 200 ...
Page 440: ...ENGINEERING MANULA OF AUTOMATIC CONTROL INDIVIDUAL ROOM CONTROL APPLICATIONS 430 ...
Page 516: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 506 Notes ...
Page 517: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 507 Notes ...
Page 518: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL GENERAL ENGINEERING DATA 508 ...